E6581160
20
3
3.1.1 How to start and stop
[Example of a EOQF setting procedure]
Key operated LED display Operation
Displays the operation frequency (operation stopped).
(When standard monitor display selection H= [Operation
frequency])
CWJ
Displays the first basic parameter [History (CWJ)].
EOQF
Press either the or key to select “EOQF”.
Press ENTER key to display the parameter setting. (Default setting:).
Change the parameter to (terminal board) by pressing the key.
⇔EOQF
Press the ENTER key to save the changed parameter. EOQF and the
parameter set value are displayed alternately.
(1)Start and stop using the operation panel keys (EOQF=)
Use the and keys on the operation panel to start and stop the motor.
: Motor starts. : Motor stops.
✩
✩✩
✩ To switch between forward run and reverse run from the control panel, the parameter fr
(forward/reverse run selection) needs to be set to 2 or 3.
(2)RUN/STOP by means of an external signal to the terminal board (EOQF=):
Sink (Negative) logic
Use external signals to the inverter terminal board to start and stop the motor.
Frequency
ON
OFF
F-CC
Slow down
and stop
F
FF
F
Short and terminals: run forward
Open and terminals: slow down and stop
CC
F CC
(3)Coast stop
The standard default setting is for slowdown stop. To
make a coast stop, assign a "1(ST)" terminal function
to an idle terminal using the programmable terminal
function.
Change to H=.
For coast stop, open the ST-CC when stopping the
motor in the state described at left.The monitor on the
inverter at this time will display QHH.
Motor
speed
ON
OFF
ON
OFF
F-CC
ST-CC
Coast stop
MODE