E6581160
66
7
Q Table of input terminal functions 2
Function
No.
Code Function Action
34 F+SS3+AD2 Combination of forward run, preset-speed
command 3 and acceleration/deceleration 2
ON: Simultaneous input from F, SS3 and AD2
35 R+SS3+AD2 Combination of reverse run, preset-speed
command 3 and acceleration/deceleration 2
ON: Simultaneous input from R, SS3 and AD2
36 F+SS4+AD2 Combination of forward run, preset-speed
command 4 and acceleration/deceleration 2
ON: Simultaneous input from F, SS4 and AD2
37 R+SS4+AD2 Combination of reverse run, preset-speed
command 4 and acceleration/deceleration 2
ON: Simultaneous input from R, SS4 and AD2
38 FCHG Frequency command forced switching
ON: H (If H = )
OFF: HOQF
39 VF2 No.2 Switching of V/F setting ON: No.2 V/F setting
(RV=0, H, H, H, H)
OFF: No.1 V/F setting
(Set value of RV, XN, XNX, XD, VJT)
40 MOT2 No.2 motor switching
(VF2+AD2+OCS2)
ON: No.2 motor
(RV=0, H, H, H, H,
H, H, H, H)
OFF: No.1 motor (Set value of RV, XN, XNX,
XD, VJT, CEE, FGE, H, H)
41 UP Frequency UP signal input from external contacts ON: Increase in frequency
42 DOWN Frequency DOWN signal input from external
contacts
ON: Reduction in frequency
43 CLR Frequency UP/DOWN cancellation signal input
from external contacts
OFF→ON: Resetting of UP/DOWN frequency by
means of external contacts
44 CLR+RES Combination of frequency UP/DOWN cancellation
and reset by means of external contacts
ON: Simultaneous input from CLR and RES
45 EXTN Inversion of trip stop command from external
device
OFF: G Trip stop
46 OH Thermal trip stop signal input from external device ON: QJ Trip stop
47 OHN Inversion of thermal trip stop command from
external device
OFF: QJ Trip stop
48 SC/LC Forced switching from remote to local control Enabled when remote control is exercised
ON: Local control (setting of cmod, HOQF and
H)
OFF: Remote control
49 HD Operation holding (stop of 3-wire operation) ON: F (forward run)/R: (reverse run) held, 3-wire
operation
OFF: Slowdown stop
50 CMTP Forced switching of command mode and terminal
board command
ON: Terminal board operation
OFF: Setting of EOQF
51 CKWH Display cancellation of the cumulative power
amount (kWh)
ON: Monitor display cancellation of the cumulative
power amount (kWh)
52 FORCE Forced operation (factory configuration required) ON: Forced operation mode in which operation is
not stopped in the event of the occurrence of
a soft fault (preset speed operation frequency
15) To use this function, the inverter needs to
be so configured at the factory.
OFF: Normal operation
53 FIRE Fire-speed control ON: Fire-speed operation (preset speed operation
frequency 15)
OFF: Normal operation
Note. When function 1, 10-12, 15-17, 38, 41-45 or 48 is assigned to an input terminal board, the input terminal
board is enabled even if the parameter command mode selection cmod is set at 1 (panel).