6
Q AIC, Fuse and Wire sizes
Voltage
class
Capacity of
applicable motor
(kW)
Inverter model
AIC (A)
(Interrupting capacity)
Fuse class and current
(A)
Wire sizes of
power circuit
0.2 VFS11S-2002PL AIC 1000A CC/J 6A max. AWG 14
0.4 VFS11S-2004PL AIC 1000A CC/J 10A max. AWG 14
0.75 VFS11S-2007PL AIC 1000A CC/J 15A max. AWG 14
1.5 VFS11S-2015PL AIC 1000A CC/J 20A max. AWG 12
Single-phase
240V class
2.2 VFS11S-2022PL AIC 1000A CC/J 30A max. AWG 10
0.4 VFS11-2004PM AIC 5000A CC/J 6A max. AWG 14
0.55 VFS11-2005PM AIC 5000A CC/J 10A max. AWG 14
0.75 VFS11-2007PM AIC 5000A CC/J 10A max. AWG 14
1.5 VFS11-2015PM AIC 5000A CC/J 15A max. AWG 14
2.2 VFS11-2022PM AIC 5000A CC/J 20A max. AWG 12
4.0 VFS11-2037PM AIC 5000A J 35A max. AWG 10
5.5 VFS11-2055PM AIC 22000A J 50A max. AWG 8
7.5 VFS11-2075PM AIC 22000A J 60A max. AWG 6
11 VFS11-2110PM AIC 22000A J 80A max. AWG 4
Three-phase
240V class
15 VFS11-2150PM AIC 22000A J 110A max. AWG 6x2
0.4 VFS11-4004PL AIC 5000A CC/J 3A max. AWG 14
0.75 VFS11-4007PL AIC 5000A CC/J 6A max. AWG 14
1.5 VFS11-4015PL AIC 5000A CC/J 10A max. AWG 14
2.2 VFS11-4022PL AIC 5000A CC/J 15A max. AWG 14
4.0 VFS11-4037PL AIC 5000A CC/J 20A max. AWG 12
5.5 VFS11-4055PL AIC 22000A CC/J 30A max. AWG 10
7.5 VFS11-4075PL AIC 22000A J 35A max. AWG 8
11 VFS11-4110PL AIC 22000A J 50A max. AWG 8
Three-phase
500V class
15 VFS11-4150PL AIC 22000A J 70A max. AWG 6
0.75 VFS11-6007P AIC 5000A CC/J 6A max. AWG 14
1.5 VFS11-6015P AIC 5000A CC/J 6A max. AWG 14
2.2 VFS11-6022P AIC 5000A CC/J 10A max. AWG 14
4.0 VFS11-6037P AIC 5000A CC/J 15A max. AWG 14
5.5 VFS11-6055P AIC 22000A CC/J 20A max. AWG 10
7.5 VFS11-6075P AIC 22000A CC/J 25A max. AWG 10
11 VFS11-6110P AIC 22000A J 30A max. AWG 8
Three-phase
600V class
15 VFS11-6150P AIC 22000A J 45A max. AWG 8
6.2.4 Motor thermal protection
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor. In
case of multi motor operation with one inverter, thermal relay should be connected to each motor.