Toshiba VF-S11 Portable Generator User Manual


 
E6581160
56
7
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0273 Jumping width 2 Hz 0.1/0.01 0.0-30.0 0.0 6.10
H
0274 Jump frequency 3 Hz 0.1/0.01 0.0-HJ 0.0
H
0275 Jumping width 3 Hz 0.1/0.01 0.0-30.0 0.0
H
0287 Preset-speed
operation frequency
8
Hz 0.1/0.01 NN-WN 0.0
H
0288 Preset-speed
operation frequency
9
Hz 0.1/0.01 NN-WN 0.0
H
0289 Preset-speed
operation frequency
10
Hz 0.1/0.01 NN-WN 0.0
H
0290 Preset-speed
operation frequency
11
Hz 0.1/0.01 NN-WN 0.0
H
0291 Preset-speed
operation frequency
12
Hz 0.1/0.01 NN-WN 0.0
H
0292 Preset-speed
operation frequency
13
Hz 0.1/0.01 NN-WN 0.0
H
0293 Preset-speed
operation frequency
14
Hz 0.1/0.01 NN-WN 0.0
5.14
H
0294 Preset-speed
operation frequency
15
(Fire-speed)
Hz 0.1/0.01 NN-WN 0.0 5.14
6.11.2
Operation mode parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0300 PWM carrier
frequency
kHz 0.1/0.1 2.0 - 16.0 12.0 6.12
H
0301 Auto-restart
control selection
- - 0: Disabled
1: At auto-restart after momentary
stop
2: ST terminal on or off
3: At auto-restart or when turning ST-
CC on or off
4: At start-up
0 6.13.1
H
0302 Regenerative
power ride-
through control
(Deceleration
stop)
- - 0: Disabled
1: Automatic setting
2: Slowdown stop
0 6.13.2
H
0303 Retry selection
(number of times)
Times 1/1 0: Disabled
1-10
0 6.13.3
H
0304 Dynamic braking
selection
- - 0: Disabled
1: Enabled (Resistor overload
protection enabled)
0 6.13.4
H
0305 Overvoltage limit
operation
(Slowdown stop
mode selection)
- - 0: Enabled
1: Disabled
2: Enabled (Quick deceleration)
3: Enabled (Dynamic quick
deceleration)
2 6.13.5