Toshiba VF-S11 Portable Generator User Manual


 
E6581160
32
4
Q Example of parameter setting
Steps in setting are as follows
(Example of changing the dynamic braking selection H from 0 to 1.)
Key operated LED display Operation
.
Displays the operation frequency (operation stopped).
(When standard monitor display selection H= [Operation
frequency])
CWJ
The first basic parameter “CWJ” (history function) is displayed.
H
Press either the or the to change to the parameter group
H.
H
Press the ENTER key to display the first extended parameter
H.
H
Press the key to change to the dynamic braking selection H.
Pressing the ENTER key allows the reading of parameter setting.
Press the key to change the dynamic braking selection from to
.
H
Pressing the ENTER key alternately flashes on and off the parameter
and changed value and allows the save of those values.
If there is anything you do not understand during this operation, press the MODE key several times to
start over from the step of CWJ display.
For details on the function of each parameter, refer to the full version of English manual (E6581158).
4.2.3 Search and resetting of changed parameters (I4W)
Automatically searches for only those parameters that are programmed with values different from the
standard default setting and displays them in the user parameter group I4W. Parameter setting can also be
changed within this group.
Notes on operation
If you reset a parameter to its factory default, the parameter will no longer appear in I4W.
fO, f470-f473 are not appeared, if the value of these parameters are changed.
Q How to search and reprogram parameters
The operations of search and resetting of parameters are as follows.
Key operated LED display Operation

Displays the operation frequency (operation stopped).
(When standard monitor display selection H= [Operation
frequency])
CWJ
The first basic parameter “CWJ” (history function) is displayed.
ITW Press or key to select I4W.
MODE
MODE