E6581160
26
3
Operation frequency setting, running and stopping using external
signals.
(1) Wiring
(2) Parameter setting
Title Function Programmed value
EOQF
Command mode selection 0
HOQF
Frequency setting mode selection 1or2
(3) Operation
Run/stop: ON/OFF input to F-CC, R-CC. (Set SW1 to Sink logic)
Frequency setting: VIA and VIB: 0-10Vdc (External potentiometer)
VIA: Input 4-20mAdc.
Note) Use the VIA slide switch to switch between voltage and current to the VIA terminal.
Voltage input: V side
Current input: I side
* 600V models have no noise filter inside.
Braking
circuit
Motor
IM
F
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Run forward signal
R
PO PC/-
PB
PA/+
Power circuit
Run backward signal
MCCB
CC
VIA
Common
Current signal: 4∼20mA
CC
VIB
VIA PP
Voltage signal: 0∼10V
External potentiometer
(Otherwise, input voltage signal (0~10V) between the terminals VIA-CC.)
Noise
filter
*
Ex.4