7
Acceleration/deceleration time parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0500 Acceleration time
2
s 0.1/0.1 0.0-3200 10.0
H
0501 Deceleration time
2
s 0.1/0.1 0.0-3200 10.0
H
0502 Acceleration/decel
eration 1 pattern
-- 0
H
0503 Acceleration/decel
eration 2 pattern
--
0: Linear
1: S-pattern 1
2: S-pattern 2
0
H
0504 Acceleration/decel
eration selection
(1, 2 , 3)
- - 1: Acceleration/deceleration 1
2: Acceleration/deceleration 2
3: Acceleration/deceleration 3
1
H
0505 Acceleration/decel
eration 1 and 2
switching
frequency
Hz 0.1/0.01 0.0-WN 0.0
H
0506 S-pattern lower-
limit adjustment
amount
% 1/1 0-50 10
6.18
H
0507 S-pattern upper-
limit adjustment
amount
% 1/1 0-50 10
H
0510 Acceleration time
3
s 0.1/0.1 0.0-3200 10.0
H
0511 Deceleration time
3
s 0.1/0.1 0.0-3200 10.0
H
0512 Acceleration/decel
eration 3 pattern
- - 0: Linear
1: S-pattern 1
2: S-pattern 2
0
H
0513 Acceleration/decel
eration 2 and 3
switching
frequency
Hz 0.1/0.01 0.0-WN 0.0
6.18
Protection parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0601 Stall prevention
level 1
%
(A)
1/1
10-199
200 (disabled)
150
6.19.2
H
0602
Inverter trip
retention selection
- - 0: Canceled with the power off
1: Still retained with the power off
0 6.19.3
H
0603 Emergency stop
selection
- - 0: Coast stop
1: Slowdown stop
2: Emergency DC braking
0
6.19.4
H
0604 Emergency DC
braking time
s
0.1/0.1 0.0-20.0
1.0
6.19.4
H
0605
Output phase
failure detection
mode selection
-
-
0: Disabled
1: At start-up (only one time after
power is turned on)
2: At start-up (each time)
3: During operation
4: At start-up + during operation
5: Detection of cutoff on output side
0
6.19.5
H
0607 Motor 150%-
overload time limit
s 1/1 10-2400 300 6.19.1
H
0608 Input phase failure
detection mode
selection
- - 0: Disabled, 1: Enabled 1 6.19.6