Toshiba VF-S11 Portable Generator User Manual


 
E6581160
63
7
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0811
Communication
command point 1
setting
% 1/1 0-100 0
H
0812
Communication
command point 1
frequency
Hz 0.1/0.01 0.0-500.0 0.0
H
0813
Communication
command point 2
setting
% 1/1 0-100 100
H
0814
Communication
command point 2
frequency
Hz 0.1/0.01 0.0-500.0 50.0 (WP)
60.0
(WN, AN)
6.5.2
6.22.1
H
0829
Selection of
communication
protocol
- - 0: Toshiba inverter protocol
1: Modbus RTU protocol
0
H
0870
Block write data 1 - - 0
H
0871
Block write data 2 - -
0: No selection
1: Command information 1
2: Command information 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
0
H
0875
Block read data 1 - - 0
H
0876
Block read data 2 - - 0
H
0877
Block read data 3 - - 0
H
0878
Block read data 4 - - 0
H
0879
Block read data 5 - -
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
0
H
0880
Free notes - 1/1 0-65535 0
6.22
H
0890
Parameter for
option 1
- 1/1 0-65535 0 6.23
H
0891
Parameter for
option 2
- 1/1 0-65535 0
H
0892
Parameter for
option 3
- 1/1 0-65535 0
H
0893
Parameter for
option 4
- 1/1 0-65535 0
H
0894
Parameter for
option 5
- 1/1 0-65535 0
 
PM motor parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0910
Step-out detection
current level
%
(A)
1/1 10-150 100
H
0911
Step-out detection
time
s 1/1 0.0: No detection
0.1-25.0
0.0
H
0912
High-speed torque
adjustment
coefficient
- 0.01/0.01 0.00-650.0 0.00
6.24