E6581160
9
1
1.2 Contents of the product
Explanation of the name plate label. Always shut power off first then check the ratings label of inverter held in a
cabinet.
Type Form
VFS11S- 2007PLE- WN -A22
Model name
TOSVERT
VF-S11series
Number of
power phases
S: sin
g
le-
p
hase
None:
three-
p
hase
Applicable motor
capacity
002 : 0.2kW
004 : 0.4kW
005 : 0.55kW
007 : 0.75kW
015 : 1.5kW
022 : 2.2kW
037 : 3.7kW
055 : 5.5kW
075 : 7.5kW
110 : 11kW
150 : 15kW
Additional functions I
None: No filter inside
M: Built-in basic filter
L: Built-in
high-attenuation
EMI filter
Operation panel
P: Provided
Default interface
logic*
WN, AN: Negative
WP : Positive
Special specification code
A
:
is the number
Input (AC) voltage
2 : 200V to 240V
4 : 380V to 500V
6 : 525V to 600V
Additional function II
None: Standard product
E: Enclosed type
U: Open type
R: With a built-in RS-485
circuit board
* This code represents the factory default logic setting. You can switch from one input/output logic to the other using
slide switch SW1.
1.3 Installation
Install the inverter in a well-ventilated indoor place and mount it on a flat metal plate in portrait orientation.
If you are installing more than one inverter, the separation between inverters should be at least 5 centimeters,
and they should be arranged in horizontal rows. If the inverters are horizontally arranged with no space
between them (side-by-side installation), peel off the ventilation seals on top of the inverter. It is necessary to
decrease the current if the inverter is operated at over 50°C.
•
••
•Standard installation •
••
•Side-by-side installation
5 cm or more
5 cm or more
10 cm or more
10 cm or more
Remove seals on top
VFS11
VFS11 VFS11 VFS11
10 cm or more
10 cm or more
The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note: Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.