Western Telematic MPC-20VD20-2 Yard Vacuum User Manual


 
13-5
Operation via SNMP
13.5. Viewing MPC Status via SNMP
Status of various components of the MPC can be retrieved via SNMP. Plug Status, and
Environmental Status are currently supported.
13.5.1. Plug Status
The status of each plug in the system can be retrieved using the command below.
plugTable::plugStatus – The status of the plug.
0 – Plug is OFF
1 – Plug is ON
13.5.2. Unit Environment Status
The environment status can be retrieved for various variables for all of the MPC units in
the system. The environmentUnitTable contains four rows, one row for each unit in the
system (LOCAL, AUX1, AUX2, AUX3.)
environmentUnitTable::environmentUnitName – The unit (LOCAL, AUX1,
AUX2, or AUX3.)
environmentUnitTable::environmentUnitTemperature – The temperature
of the given unit.
environmentUnitTable::environmentUnitCurrentA – Unit's total current
for Branch A. Note that Current will be reported in tenths of an Amp (divide result
by ten to determine value in Amps.)
environmentUnitTable::environmentUnitVoltageA – Unit voltage for
Branch A
environmentUnitTable::environmentUnitPowerA – Power drawn by
Branch A
environmentUnitTable::environmentUnitCurrentB – Unit's total current
for Branch B. Note that Current will be reported in tenths of an Amp (divide result
by ten to determine value in Amps.)
environmentUnitTable::environmentUnitVoltageB – Unit voltage for
Branch B
environmentUnitTable::environmentUnitPowerB – Power drawn on
Branch B