13-2
Operation via SNMP
13.3. Configuration via SNMP
MPC User accounts can be viewed, created, modified, and deleted via SNMP. User
accounts are arranged in a table of 128 rows, and indexed 1-128. User account
parameters, as seen through the SNMP, are summarized below.
• userTable::userName – 32 character username
• userTable::userPassword – 16 character password
• userTable::userAccessLevel – Account access level.
0 – View Access
1 – User Access
2 – Superuser Access
3 – Administrator Access
• userTable::userLocalAccess – A string of 20 characters, with one character
for each of the 20 possible plugs on the LOCAL MPC unit. A ‘0’ indicates that the
account does not have access to the plug, and a ‘1’ indicates that the user does
have access to the plug.
• userTable::userAux1Access – A string of 20 characters, with one character
for each of the 20 possible plugs on the AUX1 MPC unit. A ‘0’ indicates that the
account does not have access to the plug, and a ‘1’ indicates that the user does
have access to the plug.
• userTable::userAux2Access – A string of 20 characters, with one character
for each of the 20 possible plugs on the AUX2 MPC unit. A ‘0’ indicates that the
account does not have access to the plug, and a ‘1’ indicates that the user does
have access to the plug.
• userTable::userAux3Access – A string of 20 characters, with one character
for each of the 20 possible plugs on the AUX3 MPC unit. A ‘0’ indicates that the
account does not have access to the plug, and a ‘1’ indicates that the user does
have access to the plug.
• userTable::userGroupAccess – A string of 54 characters, with one character
for each of the 54 possible plug groups in the system. A ‘0’ indicates that the
account does not have access to the plug group, and a ‘1’ indicates that the user
does have access to the plug group.
• userTable::userSerialAccess – Access to the serial interface
0 – No access
1 – Access
• userTable::userTelnetSshAccess – Access to the Telnet/SSH interface
0 – No access
1 - Access
• userTable::userWebAccess – Access to the Web interface
0 – No access
1 - Access
• userTable::userCurrentMetering – Access to the systems current/power
metering
0 – No access
1 – Access
• userTable::userCallbackNum – 32 character callback number for account
• userTable::userSubmit – Set to 1 to submit changes.