Western Telematic MPC-20VD20-2 Yard Vacuum User Manual


 
2-3
Unit Description
BUS
A
BUS
B
BUS
A
BUS
B
A-1 A-2
A-3 A-4 A-5
A-6
A-7 A-8
B-1
B-2
B-3
B-4
B-5
B-6 B-7
B-8
10/100 BaseT
ACT
A
B
ALARM
LINK
1
3
4
3
2
6
5
7
8
6
Figure 2.2: MPC-H Series - Back Panel (Model MPC-16H-1 Shown)
2.2. MPC-H Series - Back Panel
As shown in Figure 2.2, the MPC-H Series Back Panel includes the following
components:
1. Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies power to
MPC control functions and the Circuit “A” outlets. Also includes cable keeper
(not shown.)
Note: MPC-18H series units feature a single Power Inlet.
2. Power Circuit B - Power Inlet: An IEC320-C20 AC inlet which supplies power to
MPC control functions and the Circuit “B” outlets. Also includes cable keeper
(not shown.) (Not present on MPC-18H series units.)
3. Power Circuit A - Circuit Breaker(s): Note that on MPC-16H and MPC-18H
models, there are two circuit breakers for each power circuit. The circuit breakers
are rated as follows:
MPC-8H-1, MPC-16H-1 and MPC-18H-1: 20 Amp Circuit Breaker(s).
MPC-8H-2, MPC-16H-2 and MPC-18H-2: 16 Amp Circuit Breaker(s).
4. Power Circuit A - Switched Outlets: AC Outlets that can be switched On, Off or
rebooted in response to user commands:
MPC-8H-1: Four (4) each, NEMA 5-20R Outlets.
MPC-8H-2: Four (4) each, IEC320-C13 Outlets.
MPC-16H-1: Eight (8) each, NEMA 5-20R Outlets.
MPC-16H-2: Eight (8) each, IEC320-C13 Outlets.
MPC-18H-1: Eight (8) each, NEMA 5-20R Outlets.
MPC-18H-2: Eight (8) each, IEC320-C13 Outlets.