GE Multilin 489 Generator Management Relay 6-43
6 COMMUNICATIONS 6.5 DNP POINT LISTS
6
6.5DNP POINT LISTS 6.5.1 BINARY INPUT / BINARY INPUT CHANGE (OBJECTS 01/02)
The point list for Binary Inputs (Object 01) and Binary Input Change (Object 02) is shown below:
Table 6–5: BINARY INPUT POINTS (SHEET 1 OF 4)
INDEX DESCRIPTION EVENT
CLASS
0 Relay In Service Class 1
1 Trip Condition Active Class 1
2 Alarm Condition Active Class 1
3 Simulation Mode Enabled Class 1
4 Breaker Is Open Class 1
5 Breaker Is Closed Class 1
6 Hot Stator Fault Active Class 1
7 Negative Sequence Fault Active Class 1
8 Ground Fault Active Class 1
9 Loss Of Field Fault Active Class 1
10 VT Failure Detected Class 1
11 Breaker Failure Detected Class 1
12 Relay 1 Trip Operated Class 1
13 Relay 2 Auxiliary Operated Class 1
14 Relay 3 Auxiliary Operated Class 1
15 Relay 4 Auxiliary Operated Class 1
16 Relay 5 Alarm Operated Class 1
17 Relay 6 Service Operated Class 1
18 Setpoint Access Input Closed Class 1
19 Breaker Status Input Closed Class 1
20 Assignable Input 1 Closed Class 1
21 Assignable Input 2 Closed Class 1
22 Assignable Input 3 Closed Class 1
23 Assignable Input 4 Closed Class 1
24 Assignable Input 5 Closed Class 1
25 Assignable Input 6 Closed Class 1
26 Assignable Input 7 Closed Class 1
27 Trip Coil Supervision - Coil Detected Class 1
28 … Reserved …
↓↓
39 … Reserved …
40 Assignable Input 1 Trip Active /
Latched
Class 1
41 Assignable Input 2 Trip Active /
Latched
Class 1
42 Assignable Input 3 Trip Active /
Latched
Class 1
43 Assignable Input 4 Trip Active /
Latched
Class 1
44 Assignable Input 5 Trip Active /
Latched
Class 1
45 Assignable Input 6 Trip Active /
Latched
Class 1
46 Assignable Input 7 Trip Active /
Latched
Class 1
47 Sequential Trip Active or Latched Class 1
48 Field-Breaker Discrepancy Trip Active
or Latched
Class 1
49 Tachometer Trip Active or Latched Class 1
50 Offline O/C Trip Active or Latched Class 1
51 Inadvertent Energization Trip Active or
Latched
Class 1
52 Phase O/C Trip Active or Latched Class 1
53 Neg. Seq. O/C Trip Active or Latched Class 1
54 Ground O/C Trip Active or Latched Class 1
55 Phase Differential Trip Active or
Latched
Class 1
56 Undervoltage Trip Active or Latched Class 1
57 Overvoltage Trip Active or Latched Class 1
58 Volts/Hertz Trip Active or Latched Class 1
59 Phase Reversal Trip Active or Latched Class 1
60 Underfrequency Trip Active or Latched Class 1
61 Overfrequency Trip Active or Latched Class 1
62 Neutral O/V (Fund) Trip Active /
Latched
Class 1
63 Neutral U/V (3
rd
Harmonic) Trip Active
or Latched
Class 1
64 Reactive Power Trip Active or Latched Class 1
65 Reverse Power Trip Active or Latched Class 1
66 Low Fwd Power Trip Active or Latched Class 1
67 Thermal Model Trip Active or Latched Class 1
68 RTD #1 Trip Active or Latched Class 1
69 RTD #2 Trip Active or Latched Class 1
70 RTD #3 Trip Active or Latched Class 1
71 RTD #4 Trip Active or Latched Class 1
72 RTD #5 Trip Active or Latched Class 1
73 RTD #6 Trip Active or Latched Class 1
74 RTD #7 Trip Active or Latched Class 1
75 RTD #8 Trip Active or Latched Class 1
76 RTD #9 Trip Active or Latched Class 1
77 RTD #10 Trip Active or Latched Class 1
78 RTD #11 Trip Active or Latched Class 1
79 RTD #12 Trip Active or Latched Class 1
80 Analog Input 1 Trip Active or Latched Class 1
81 Analog Input 2 Trip Active or Latched Class 1
82 Analog Input 3 Trip Active or Latched Class 1
83 Analog Input 4 Trip Active or Latched Class 1
84 Loss of Excitation Circle 1 Trip Active
or Latched
Class 1
Table 6–5: BINARY INPUT POINTS (SHEET 2 OF 4)
INDEX DESCRIPTION EVENT
CLASS