GE Multilin 489 Generator Management Relay 5-29
5 ACTUAL VALUES 5.8 DIAGNOSTICS
5
TOP OF LIST: This message will indicate when the top of subgroup has been reached.
END OF LIST: This message will indicate when the bottom of a subgroup has been reached.
NO ALARMS ACTIVE: If an attempt is made to enter the Alarm Status message subgroup, but there are no active
alarms, this message will appear.
THIS FEATURE NOT PROGRAMMED: If an attempt is made to enter an actual value message subgroup, when the
setpoints are not configured for that feature, this message will appear.
THIS PARAMETER IS ALREADY ASSIGNED:
A given analog output parameters can only be assigned to one output.
If an attempt is made to assign a parameter to a second output, this message will appear.
THAT INPUT ALREADY USED FOR TACHOMETER: If a digital input is assigned to the tachometer function, it cannot
be used for any other digital input function. If an attempt is made to assign a digital input to a function when it is already
assigned to tachometer, this message will appear.
TACHOMETER MUST USE INPUT 4, 5, 6, or 7: Only digital inputs 4, 5, 6, or 7 may be used for the tachometer func-
tion. If an attempt is made to assign inputs 1,2,3, or 4 to the tachometer function, this message will appear.
THAT DIGITAL INPUT IS ALREADY IN USE: If an attempt is made to assign a digital input to tachometer when it is
already assigned to another function, this message will appear.
To edit use VALUE UP or VALUE DOWN key:
If a numeric key is pressed on a setpoint parameter that is not
numeric, this message will prompt the user to use the value keys.
GROUP 1 SETPOINT HAS BEEN STORED: This message appear each time a setpoint has been altered and stored
to setpoint Group 1 as shown on the display.
GROUP 2 SETPOINT HAS BEEN STORED: This message appear each time a setpoint has been altered and stored
to setpoint Group 2 as shown on the display.