GE 489 Portable Generator User Manual


 
4-52 489 Generator Management Relay GE Multilin
4.9 S8 RTD TEMPERATURE 4 SETPOINTS
4
4.9.4 RTD 11
PATH: SETPOINTS ÖØ S8 RTD TEMPERATURE ÖØ RTD #11
RTD 11 defaults to Other RTD type. The Other selection allows the RTD to be used to monitor any temperature that might
be required, either for a process or additional bearings or other. There are individual alarm and trip configurations for this
RTD. Trip voting has been added for extra reliability in the event of RTD malfunction. If enabled, a second RTD must also
exceed the trip temperature of the RTD being checked before a trip will be issued. If the RTD is chosen to vote with itself,
the voting feature is disabled. The RTD name may be changed if desired.
RTD #11
[ENTER] for more
RTD #11 APPLICATION:
Other
Range: Stator, Bearing, Ambient, Other, None
RTD #11 NAME:
Range: 8 alphanumeric characters
RTD #11 ALARM:
Off
Range: Off, Latched, Unlatched
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to 5.
RTD #11 ALARM
TEMPERATURE: 80°C
Range: 1 to 250°C in steps of 1
RTD #11 ALARM
EVENTS: Off
Range: On, Off
RTD #11 TRIP:
Off
Range: Off, Latched, Unlatched
RTD #11 TRIP VOTING:
RTD #11
Range: RTD #1 to RTD #12
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to 4
RTD #11 TRIP
TEMPERATURE: 90°C
Range: 1 to 250°C in steps of 1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE