6-18 489 Generator Management Relay GE Multilin
6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS
6
DIGITAL INPUTS / GENERAL INPUT F
12B0 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
12B1 ASSERTED DIGITAL INPUT STATE 0 to 1 1 – F131 0
12B2 INPUT NAME 0 to 12 1 – F22 _
12B8 BLOCK INPUT FROM ONLINE 0 to 5000 1 s F1 0
12B9 GENERAL INPUT F CONTROL 0 to 1 1 – F105 0
12BA PULSED CONTROL RELAY DWELL TIME 0 to 250 1 s F2 0
12BB ASSIGN CONTROL RELAYS (1-5) 0 to 4 1 – F50 0
12BC GENERAL INPUT F CONTROL EVENTS 0 to 1 1 – F105 0
12BD GENERAL INPUT F ALARM 0 to 2 1 – F115 0
12BE ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
12BF GENERAL INPUT F ALARM DELAY 1 to 50000 1 s F2 50
12C0 GENERAL INPUT F ALARM EVENTS 0 to 1 1 – F105 0
12C1 GENERAL INPUT F TRIP 0 to 2 1 – F115 0
12C2 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
12C3 GENERAL INPUT F TRIP DELAY 1 to 50000 1 s F2 50
DIGITAL INPUTS / GENERAL INPUT G
12D0 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
12D1 ASSERTED DIGITAL INPUT STATE 0 to 1 1 – F131 0
12D2 INPUT NAME 0 to 12 1 – F22 _
12D8 BLOCK INPUT FROM ONLINE 0 to 5000 1 s F1 0
12D9 GENERAL INPUT G CONTROL 0 to 1 1 – F105 0
12DA PULSED CONTROL RELAY DWELL TIME 0 to 250 1 s F2 0
12DB ASSIGN CONTROL RELAYS (1-5) 0 to 4 1 – F50 0
12DC GENERAL INPUT G CONTROL EVENTS 0 to 1 1 – F105 0
12DD GENERAL INPUT G ALARM 0 to 2 1 – F115 0
12DE ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
12DF GENERAL INPUT G ALARM DELAY 1 to 50000 1 s F2 50
12E0 GENERAL INPUT G ALARM EVENTS 0 to 1 1 – F105 0
12E1 GENERAL INPUT G TRIP 0 to 2 1 – F115 0
12E2 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
12E3 GENERAL INPUT G TRIP DELAY 1 to 50000 1 s F2 50
DIGITAL INPUTS / REMOTE RESET
1300 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
DIGITAL INPUTS / TEST INPUT
1310 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
DIGITAL INPUTS / THERMAL RESET
1320 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
DIGITAL INPUTS / DUAL SETPOINTS
1340 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
1341 ACTIVE SETPOINT GROUP 0 to 1 1 – F118 0
1342 EDIT SETPOINT GROUP 0 to 1 1 – F118 0
DIGITAL INPUTS / SEQUENTIAL TRIP
1360 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
1361 SEQUENTIAL TRIP TYPE 0 to 1 1 – F206 0
1362 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
1363 SEQUENTIAL TRIP LEVEL 2 to 99 1 ×Rated MW F14 5
1365 SEQUENTIAL TRIP DELAY 2 to 1200 1 s F2 10
DIGITAL INPUTS / FIELD-BKR DISCREP.
1380 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
1381 FIELD STATUS CONTACT 0 to 1 1 – F109 0
1382 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
1383 FIELD-BKR DISCREP. TRIP DELAY 1 to 5000 1 s F2 10
DIGITAL INPUTS / TACHOMETER
13A0 ASSIGN DIGITAL INPUT 0 to 7 1 – F210 0
13A1 RATED SPEED 100 to 3600 1 RPM F1 3600
13A2 TACHOMETER ALARM 0 to 2 1 – F115 0
13A3 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
13A4 TACHOMETER ALARM SPEED 101 to 175 1 %Rated F1 110
13A5 TACHOMETER ALARM DELAY 1 to 250 1 s F1 1
13A6 TACHOMETER ALARM EVENTS 0 to 1 1 – F105 0
13A7 TACHOMETER TRIP 0 to 2 1 – F115 0
13A8 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
13A9 TACHOMETER TRIP SPEED 101 to 175 1 %Rated F1 110
13AA TACHOMETER TRIP DELAY 1 to 250 1 s F1 1
Table 6–1: 489 MEMORY MAP (SHEET 9 OF 24)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–33