GE Multilin 489 Generator Management Relay 3-9
3 USER INTERFACES 3.2 SOFTWARE INTERFACE
3
5. The 489PC software automatically lists all filenames beginning with 32. Select the appropriate file and click OK to con-
tinue.
6. 489PC prompts with the following dialog box. This will be the last chance to cancel the firmware upgrade before the
flash memory is erased. Click Yes to continue or No to cancel the upgrade.
7. The software automatically puts the relay into “upload mode” and begins loading the selected firmware file. Upon com-
pletion, the relay is placed back into “normal mode”.
8. When the 489 firmware update is complete, the relay will not be in service and will require programming. To communi-
cate with the relay via the RS485 ports, the Slave Address, Baud Rate, and Parity will have to be manually pro-
grammed. When communications is established, the saved setpoints will have to be reloaded back into the 489. See
the next section for details.
c) LOADING SETPOINTS FROM A FILE
An error message will occur when attempting to download a setpoint file with a revision number that does
not match the relay firmware. If the firmware has been upgraded since saving the setpoint file, see Section
e): Upgrading Setpoint Files to a New Revision on page 3–10 for instructions on changing the revision
number of a setpoint file.
The following procedure demonstrates how to load setpoints from a file:
1. Select the File > Open menu item.
2. 489PC will launch the Open window and list all filenames in the 489 default directory with the 489 extension. Select the
setpoint file to download and click OK to continue.
3. Select the File > Send Info to Relay menu item. 489PC will prompt to confirm or cancel the setpoint file load. Click
Yes to update the 489 setpoints.
808733A1.CDR
32 I 151 A8 .000
Modification Number (000 = none)
GE Multilin use only
Firmware Revision
Required 489 hardware revision
Product code (32 =489 Generator Management Relay)
WARNING