GE 489 Portable Generator User Manual


 
6-20 489 Generator Management Relay GE Multilin
6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS
6
1624 FLEXCURVE TRIP TIME AT 4.00 ×PU 0 to 65535 1 ms F1 65535
1625 FLEXCURVE TRIP TIME AT 4.10 ×PU 0 to 65535 1 ms F1 65535
1626 FLEXCURVE TRIP TIME AT 4.20 ×PU 0 to 65535 1 ms F1 65535
1627 FLEXCURVE TRIP TIME AT 4.30 ×PU 0 to 65535 1 ms F1 65535
1628 FLEXCURVE TRIP TIME AT 4.40 ×PU 0 to 65535 1 ms F1 65535
1629 FLEXCURVE TRIP TIME AT 4.50 ×PU 0 to 65535 1 ms F1 65535
162A FLEXCURVE TRIP TIME AT 4.60 × PU 0 to 65535 1 ms F1 65535
162B FLEXCURVE TRIP TIME AT 4.70 × PU 0 to 65535 1 ms F1 65535
162C FLEXCURVE TRIP TIME AT 4.80 × PU 0 to 65535 1 ms F1 65535
162D FLEXCURVE TRIP TIME AT 4.90 × PU 0 to 65535 1 ms F1 65535
162E FLEXCURVE TRIP TIME AT 5.00 × PU 0 to 65535 1 ms F1 65535
162F FLEXCURVE TRIP TIME AT 5.10 × PU 0 to 65535 1 ms F1 65535
1630 FLEXCURVE TRIP TIME AT 5.20 ×PU 0 to 65535 1 ms F1 65535
1631 FLEXCURVE TRIP TIME AT 5.30 ×PU 0 to 65535 1 ms F1 65535
1632 FLEXCURVE TRIP TIME AT 5.40 ×PU 0 to 65535 1 ms F1 65535
1633 FLEXCURVE TRIP TIME AT 5.50 ×PU 0 to 65535 1 ms F1 65535
1634 FLEXCURVE TRIP TIME AT 5.60 ×PU 0 to 65535 1 ms F1 65535
1635 FLEXCURVE TRIP TIME AT 5.70 ×PU 0 to 65535 1 ms F1 65535
1636 FLEXCURVE TRIP TIME AT 5.80 ×PU 0 to 65535 1 ms F1 65535
1637 FLEXCURVE TRIP TIME AT 5.90 ×PU 0 to 65535 1 ms F1 65535
1638 FLEXCURVE TRIP TIME AT 6.00 ×PU 0 to 65535 1 ms F1 65535
1639 FLEXCURVE TRIP TIME AT 6.50 ×PU 0 to 65535 1 ms F1 65535
163A FLEXCURVE TRIP TIME AT 7.00 × PU 0 to 65535 1 ms F1 65535
163B FLEXCURVE TRIP TIME AT 7.50 × PU 0 to 65535 1 ms F1 65535
163C FLEXCURVE TRIP TIME AT 8.00 × PU 0 to 65535 1 ms F1 65535
163D FLEXCURVE TRIP TIME AT 8.50 × PU 0 to 65535 1 ms F1 65535
163E FLEXCURVE TRIP TIME AT 9.00 × PU 0 to 65535 1 ms F1 65535
163F FLEXCURVE TRIP TIME AT 9.50 × PU 0 to 65535 1 ms F1 65535
1640 FLEXCURVE TRIP TIME AT 10.0 ×PU 0 to 65535 1 ms F1 65535
1641 FLEXCURVE TRIP TIME AT 10.5 ×PU 0 to 65535 1 ms F1 65535
1642 FLEXCURVE TRIP TIME AT 11.0 × PU 0 to 65535 1 ms F1 65535
1643 FLEXCURVE TRIP TIME AT 11.5 × PU 0 to 65535 1 ms F1 65535
1644 FLEXCURVE TRIP TIME AT 12.0 ×PU 0 to 65535 1 ms F1 65535
1645 FLEXCURVE TRIP TIME AT 12.5 ×
PU 0 to 65535 1 ms F1 65535
1646 FLEXCURVE TRIP TIME AT 13.0 ×PU 0 to 65535 1 ms F1 65535
1647 FLEXCURVE TRIP TIME AT 13.5 ×PU 0 to 65535 1 ms F1 65535
1648 FLEXCURVE TRIP TIME AT 14.0 ×PU 0 to 65535 1 ms F1 65535
1649 FLEXCURVE TRIP TIME AT 14.5 ×PU 0 to 65535 1 ms F1 65535
164A FLEXCURVE TRIP TIME AT 15.0 × PU 0 to 65535 1 ms F1 65535
164B FLEXCURVE TRIP TIME AT 15.5 × PU 0 to 65535 1 ms F1 65535
164C FLEXCURVE TRIP TIME AT 16.0 × PU 0 to 65535 1 ms F1 65535
164D FLEXCURVE TRIP TIME AT 16.5 × PU 0 to 65535 1 ms F1 65535
164E FLEXCURVE TRIP TIME AT 17.0 × PU 0 to 65535 1 ms F1 65535
164F FLEXCURVE TRIP TIME AT 17.5 × PU 0 to 65535 1 ms F1 65535
1650 FLEXCURVE TRIP TIME AT 18.0 ×PU 0 to 65535 1 ms F1 65535
1651 FLEXCURVE TRIP TIME AT 18.5 ×PU 0 to 65535 1 ms F1 65535
1652 FLEXCURVE TRIP TIME AT 19.0 ×PU 0 to 65535 1 ms F1 65535
1653 FLEXCURVE TRIP TIME AT 19.5 ×PU 0 to 65535 1 ms F1 65535
1654 FLEXCURVE TRIP TIME AT 20.0 ×PU 0 to 65535 1 ms F1 65535
1655 OVERCURRENT CURVE MULTIPLIER 0 to 100000 1 F14 100
1657 OVERCURRENT CURVE RESET 0 to 1 1 F201 0
1658 VOLTAGE LOWER LIMIT 10 to 60 1 % F1 10
CURRENT ELEMENTS / NEGATIVE SEQUENCE
1700 NEGATIVE SEQUENCE ALARM 0 to 2 1 F115 0
1701 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
1702 NEG. SEQUENCE ALARM PICKUP 3 to 100 1 %FLA F1 3
1703 NEGATIVE SEQUENCE ALARM DELAY 1 to 1000 1 s F2 50
1704 NEGATIVE SEQUENCE ALARM EVENTS 0 to 1 1 F105 0
1705 NEGATIVE SEQUENCE O/C TRIP 0 to 2 1 F115 0
1706 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
1707 NEG. SEQUENCE O/C TRIP PICKUP 3 to 100 1 %FLA F1 8
1708 NEG. SEQUENCE O/C CONSTANT K 1 to 100 1 F1 1
1709 NEG. SEQUENCE O/C MAX. TIME 10 to 1000 1 s F1 1000
170A NEG. SEQUENCE O/C RESET RATE 0 to 9999 1 s F2 2270
Table 6–1: 489 MEMORY MAP (SHEET 11 OF 24)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–33