GE Multilin 489 Generator Management Relay 5-17
5 ACTUAL VALUES 5.3 A2 METERING DATA
5
5.3.5 DEMAND METERING
PATH: ACTUAL VALUES ÖØ A2 METERING DATA ÖØ DEMAND METERING
The values for current and power demand are shown here. This peak demand information can be cleared using the S1 489
SETUP ÖØ CLEAR DATA ÖØ CLEAR PEAK DEMAND setpoint. Demand is shown only for positive real and positive reactive
power (+Watts, +vars). Peak demand will not update if a digital input programmed as Test Input is shorted.
5.3.6 ANALOG INPUTS
PATH: ACTUAL VALUES ÖØ A2 METERING DATA ÖØ ANALOG INPUTS
The values for analog inputs are shown here. The name of the input and the units will reflect those programmed for each
input. If no analog inputs are programmed in the
S11 ANALOG I/O setpoints page, the THIS FEATURE NOT PROGRAMMED
flash message will appear when an attempt is made to enter this group of messages.
5.3.7 SPEED
PATH: ACTUAL VALUES ÖØ A2 METERING DATA ÖØ SPEED
If the Tachometer function is assigned to one of the digital inputs, its speed be viewed here. A bar graph on the second line
of this message represents speed from 0 RPM to rated speed. If no digital input is configured for tachometer, the
THIS FEA-
TURE NOT PROGRAMMED
flash message will appear when an attempt is made to enter this group of messages.
DEMAND METERING
[ENTER] for more
CURRENT
DEMAND: 0 Amps
Range: 0 to 999999 A
MW DEMAND:
0.000 MW
Range: 0.000 to 2000.000 MW. Not seen if VT
CONNECTION TYPE is programmed as None
Mvar DEMAND:
0.000 Mvar
Range: 0.000 to 2000.000 Mvar. Not seen if VT
CONNECTION TYPE is programmed as None
MVA DEMAND:
0.000 MVA
Range: 0.000 to 2000.000 MVA. Not seen if VT
CONNECTION TYPE is programmed as None
PEAK CURRENT
DEMAND: 0 Amps
Range: 0 to 999999 A
PEAK MW DEMAND:
0.000 MW
Range: 0.000 to 2000.000 MW. Not seen if VT
CONNECTION TYPE is programmed as None
PEAK Mvar DEMAND:
0.000 Mvar
Range: 0.000 to 2000.000 Mvar. Not seen if VT
CONNECTION TYPE is programmed as None
PEAK MVA DEMAND:
0.000 MVA
Range: 0.000 to 2000.000 MVA. Not seen if VT
CONNECTION TYPE is programmed as None
ANALOG INPUTS
[ENTER] for more
ANALOG I/P 1
0 Units
Range: –50000 to 50000. Message seen only if Analog
Input is programmed. Message reflects Analog
Input Name as programmed.
ANALOG I/P 2
0 Units
Range: as for ANALOG I/P 1 above
ANALOG I/P 3
0 Units
Range: as for ANALOG I/P 1 above
ANALOG I/P 4
0 Units
Range: as for ANALOG I/P 1 above
SPEED
[ENTER] for more
TACHOMETER: 0 RPM
Range: 0 to 7200 RPM. Seen only if a digital input is
configured as Tachometer.