1-8 489 Generator Management Relay GE Multilin
1.2 SPECIFICATIONS 1 INTRODUCTION
1
At temperatures lower than –20°C, the LCD contrast
may be impaired.
LONG-TERM STORAGE
Environment: In addition to the above environmental
considerations, the relay should be
stored in an environment that is dry, cor-
rosive-free, and not in direct sunlight.
Correct storage: Prevents premature component failures
caused by environmental factors such as
moisture or corrosive gases. Exposure
to high humidity or corrosive environ-
ments will prematurely degrade the elec-
tronic components in any electronic
device regardless of its use or manufac-
turer, unless specific precautions, such
as those mentioned in the Environmental
section above, are taken.
It is recommended that all relays be powered up once
per year, for one hour continuously, to avoid
deterioration of electrolytic capacitors and
subsequent relay failure.
CASE
Drawout: Fully drawout (Automatic CT shorts)
Seal: Seal provision
Door: Dust tight door
Mounting: Panel or 19" rack mount
IP Class: IP20-X
PRODUCTION TESTS
Thermal Cycling: Operational test at ambient, reducing to
–40°C and then increasing to 60°C
Dielectric Strength: 1.9 kV AC for 1 second or 1.6 kV AC for
1 minute, per UL 508.
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING ANY PRODUCTION
TESTS!
FUSE
Current Rating: 3.15 A
Type: 5 × 20 mm Slo-Blo Littelfuse, High
Breaking Capacity
Model#: 215.315
An external fuse must be used if supply voltage
exceeds 250V
TYPE TESTS
Dielectric Strength: Per IEC 255-5 and ANSI/IEEE C37.90.
2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
DO NOT CONNECT FILTER GROUND TO SAFETY
GROUND DURING TEST
Insulation Resistance: IEC255-5 500 V DC, from relays, CTs,
VTs, power supply to Safety Ground
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST
Transients: ANSI C37.90.1 oscillatory (2.5 kV/
1 MHz); ANSI C37.90.1 Fast Rise (5 kV/
10 ns); Ontario Hydro A-28M-82;
IEC255-4 Impulse/High Frequency Dis-
turbance Class III Level
Impulse Test: IEC 255-5 0.5 Joule 5 kV
RFI: 50 MHz / 15 W Transmitter
EMI: C37.90.2 Electromagnetic Interference
at 150 MHz and 450 MHz, 10V/m
Static: IEC 801-2 Static Discharge
Humidity: 90% non-condensing
Temperature: –40°C to +60°C ambient
Environment: IEC 68-2-38 Temperature/Humidity cycle
Vibration: Sinusoidal Vibration 8.0 g for 72 hrs.
PACKAGING
Shipping Box: 12” × 11” × 10” (W × H × D)
30.5cm × 27.9cm × 25.4cm
Shipping Weight: 17 lbs Max / 7.7 kg
CERTIFICATION
ISO: Manufactured under an ISO9001 regis-
tered system.
UL: UL
CSA: CSA
CE: Conforms to IEC 947-1, IEC 1010-1
NOTE
WARNING
WARNING
WARNING
WARNING
WARNING