GE 489 Portable Generator User Manual


 
6-30 489 Generator Management Relay GE Multilin
6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS
6
2B37 VOLTS/HERTZ MAX 0 to 200 1 × Rated F3 150
2B38 FREQUENCY MIN 0 to 9000 1 Hz F3 5900
2B39 FREQUENCY MAX 0 to 9000 1 Hz F3 6100
2B3C POWER FACTOR MIN –99 to 100 1 F6 80
2B3D POWER FACTOR MAX –99 to 100 1 F6 –80
2B3E REACTIVE POWER MIN –200 to 200 1 × Rated F6 0
2B3F REACTIVE POWER MAX –200 to 200 1 × Rated F6 125
2B40 REAL POWER (MW) MIN –200 to 200 1 × Rated F6 0
2B41 REAL POWER (MW) MAX –200 to 200 1 × Rated F6 125
2B42 APPARENT POWER MIN 0 to 200 1 × Rated F3 0
2B43 APPARENT POWER MAX 0 to 200 1 × Rated F3 125
2B44 ANALOG INPUT 1 MIN –50000 to 50000 1 Units F12 0
2B46 ANALOG INPUT 1 MAX –50000 to 50000 1 Units F12 50000
2B48 ANALOG INPUT 2 MIN –50000 to 50000 1 Units F12 0
2B4A ANALOG INPUT 2 MAX –50000 to 50000 1 Units F12 50000
2B4C ANALOG INPUT 3 MIN –50000 to 50000 1 Units F12 0
2B4E ANALOG INPUT 3 MAX –50000 to 50000 1 Units F12 50000
2B50 ANALOG INPUT 4 MIN –50000 to 50000 1 Units F12 0
2B52 ANALOG INPUT 4 MAX –50000 to 50000 1 Units F12 50000
2B54 TACHOMETER MIN 0 to 7200 1 RPM F1 3500
2B55 TACHOMETER MAX 0 to 7200 1 RPM F1 3700
2B56 THERM. CAPACITY USED MIN 0 to 100 1 % F1 0
2B57 THERM. CAPACITY USED MAX 0 to 100 1 % F1 100
2B58 NEUTRAL VOLT THIRD MIN 0 to 250000 1 Volts F10 0
2B5A NEUTRAL VOLT THIRD MAX 0 to 250000 1 Volts F10 450
2B5C CURRENT DEMAND MIN 0 to 2000 1 × FLA F3 0
2B5D CURRENT DEMAND MAX 0 to 2000 1 × FLA F3 125
2B5E Mar DEMAND MIN 0 to 200 1 × Rated F3 0
2B5F Mar DEMAND MAX 0 to 200 1 × Rated F3 125
2B60 MW DEMAND MIN 0 to 200 1 × Rated F3 0
2B61 MW DEMAND MAX 0 to 200 1 × Rated F3 125
2B62 MVA DEMAND MIN 0 to 200 1 × Rated F3 0
2B63 MVA DEMAND MAX 0 to 200 1 × Rated F3 125
ANALOG I/O / ANALOG INPUT 1
2C00 ANALOG INPUT1 0 to 3 1 F129 0
2C05 ANALOG INPUT1 UNITS 0 to 6 1 F22 _
2C08 ANALOG INPUT1 MINIMUM –50000 to 50000 1 Units F12 0
2C0A ANALOG INPUT1 MAXIMUM –50000 to 50000 1 Units F12 100
2C0C BLOCK ANALOG INPUT1 FROM ONLINE 0 to 5000 1 s F1 0
2C0D ANALOG INPUT1 ALARM 0 to 2 1 F115 0
2C0E ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2C0F ANALOG INPUT1 ALARM LEVEL –50000 to 50000 1 Units F12 10
2C11 ANALOG INPUT1 ALARM PICKUP 0 to 1 1 F130 0
2C12 ANALOG INPUT1 ALARM DELAY 1 to 3000 1 s F2 1
2C13 ANALOG INPUT1 ALARM EVENTS 0 to 1 1 F105 0
2C14 ANALOG INPUT1 TRIP 0 to 2 1 F115 0
2C15 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
2C16 ANALOG INPUT1 TRIP LEVEL –50000 to 50000 1 Units F12 20
2C18 ANALOG INPUT1 TRIP PICKUP 0 to 1 1 F130 0
2C19 ANALOG INPUT1 TRIP DELAY 1 to 3000 1 s F2 1
2C1A ANALOG INPUT1 NAME 0 to 12 1 F22 _
ANALOG I/O / ANALOG INPUT 2
2C40 ANALOG INPUT2 0 to 3 1 F129 0
2C45 ANALOG INPUT2 UNITS 0 to 6 1 F22 _
2C48 ANALOG INPUT2 MINIMUM –50000 to 50000 1 Units F12 0
2C4A ANALOG INPUT2 MAXIMUM –50000 to 50000 1 Units F12 100
2C4C BLOCK ANALOG INPUT2 FROM ONLINE 0 to 5000 1 s F1 0
2C4D ANALOG INPUT2 ALARM 0 to 2 1 F115 0
2C4E ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2C4F ANALOG INPUT2 ALARM LEVEL –50000 to 50000 1 Units F12 10
2C51 ANALOG INPUT2 ALARM PICKUP 0 to 1 1 F130 0
2C52 ANALOG INPUT2 ALARM DELAY 1 to 3000 1 s F2 1
2C53 ANALOG INPUT2 ALARM EVENTS 0 to 1 1 F105 0
2C54 ANALOG INPUT2 TRIP 0 to 2 1 F115 0
2C55 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
2C56 ANALOG INPUT2 TRIP LEVEL –50000 to 50000 1 Units F12 20
Table 6–1: 489 MEMORY MAP (SHEET 21 OF 24)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–33