4-72 489 Generator Management Relay GE Multilin
4.11 S10 MONITORING 4 SETPOINTS
4
4.11.5 CURRENT, MW, MVAR, AND MVA DEMAND
PATH: SETPOINTS ÖØ S10 MONITORING ÖØ CURRENT DEMAND...
CURRENT DEMAND
[ENTER] for more
CURRENT DEMAND
PERIOD: 15 min.
Range: 5 to 90 min. in steps of 1
CURRENT DEMAND
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to 5
CURRENT DEMAND
LIMIT: 1.25 x FLA
Range: 0.10 to 20.00 × FLA in steps of 0.01
CURRENT DEMAND
ALARM EVENTS: Off
Range: On, Off
MW DEMAND
[ENTER] for more
MW DEMAND
PERIOD: 15 min.
Range: 5 to 90 min. in steps of 1
MW DEMAND
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to 5
MW DEMAND
LIMIT: 1.25 x Rated
Range: 0.10 to 20.00 × Rated in steps of 0.01
MW DEMAND
ALARM EVENTS: Off
Range: On, Off
Mvar DEMAND
[ENTER] for more
Mvar DEMAND
PERIOD: 15 min.
Range: 5 to 90 min. in steps of 1
Mvar DEMAND
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to 5
Mvar DEMAND
LIMIT: 1.25 x Rated
Range: 0.10 to 20.00 × Rated in steps of 0.01
Mvar DEMAND
ALARM EVENTS: Off
Range: On, Off
MVA DEMAND
[ENTER] for more
MVA DEMAND
PERIOD: 15 min.
Range: 5 to 90 min. in steps of 1
MVA DEMAND
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to 5
MVA DEMAND
LIMIT: 1.25 x Rated
Range: 0.10 to 20.00 × Rated in steps of 0.01
MVA DEMAND
ALARM EVENTS: Off
Range: On, Off
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE