Trane BCXC-SVX01B-EN Blower User Manual


 
BCXC-SVX01B-EN 69
Maintenance
Coil Maintenance
Keep coils clean to maintain maximum performance. For operation at its highest efficiency, clean
the coil often during periods of high demand or when dirty conditions prevail. Clean the coil a
minimum of once per year to prevent dirt buildup in the coil fins, where it may not be visible.
Remove large debris from the coils and straighten fins before cleaning. Remove filters before
cleaning. Rinse coils thoroughly after cleaning. Clean the coil fins using one of these methods:
steam with detergent
hot water spray and detergent
commercially available chemical coil cleaner
NOTICE
Potential unit damage from coil cleaners!
Do not use acidic chemical coil cleaners. Also, do not use alkaline chemical coil cleaners with a
pH value greater then 8.5 (after mixing) without using an aluminum corrosion inhibitor in the
cleaning solution. Using these types of cleaners could result in equipment damage.
Inspecting and Cleaning Coils
Coils become externally fouled as a result of normal operation. Dirt on the coil surface reduces its
ability to transfer heat and can cause comfort problems, increased airflow resistance and thus
increased operating energy costs. If the coil surface dirt becomes wet, which commonly occurs
with cooling coils, microbial growth (mold) may result, causing unpleasant odors and serious
health-related indoor air quality problems.
Inspect coils at least every six months or more frequently as dictated by operating experience.
Cleaning frequently is dependent upon system operating hours, filter maintenance, and efficiency
and dirt load. Follow is the suggested method below:
Steam, Hot Water, and Cooling Coil Cleaning Procedure
1. Don the appropriate personal protective equipment (PPE).
2. Gain access to both sides of the coil section.
3. Use a soft brush to remove loose debris from both sides of the coil.
4. Use a steam cleaning machine, starting from the top of the coil and working downward. Clean
the leaving air side of the coil first, then the entering air side.
Use a block-off to prevent steam from blowing through the coil and into a dry section of the unit.
5. Repeat Step 4 as necessary. Confirm that the drain line is open following completion of the
cleaning process.
6. Allow the unit to dry thoroughly before putting the system back into service.
7. Straighten any coil fins that may be damaged with a fin rake.
8. Replace all panels and parts and restore electrical power to the unit.
9. Ensure that contaminated material does not contact other areas of the unit or building. Properly
dispose of all contaminated materials and cleaning solutions.
ƽ WARNING
Hazardous chemicals!
Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper
handling should include goggles or face shield, chemical resistant gloves, boots, apron or suit as
required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data
Sheet and follow all recommended safe handling practices. Failure to follow all safety
instructions could result in death or serious injury.