Trane BCXC-SVX01B-EN Blower User Manual


 
32 BCXC-SVX01B-EN
Installation Electrical
220/50/1
198–242 1450 1/3 20.5 3.0 15.6
1/2 25 3.6 20.5
3/4 29 5.2 25.6
1.0 38 9.3 52.2
240/50/1
216–264 1450 1/3 20.5 3.3 17.1
1/2 25 4.0 22.7
3/4 29 5.5 39.1
1.0 38 10.6 57.8
190/50/3
171–209 1450 1/3 22 1.1 5.6
380/50/3
342–418 1/2 26 1.4 7.8
3/4 28 1.7 9.8
1.0 29 2.1 14.6
1.5 34 2.8 18.7
2.0 49 3.6 27.2
415/50/3
374–456 1450 1/3 22 1.2 6.8
1/2 26 1.5 9.4
3/4 28 1.9 11.0
1.0 29 2.5 17.4
1.5 34 3.1 22.6
2.0 49 3.6 32.3
Table 14. Motor electrical data (continued)
Voltage Voltage range rpm Rated hp lb FLA LRA
Note: For two-speed units not being controlled by the Tracer™ family of controls, a 0.2-second delay for speed switching needs
to be incorporated into the control sequence.