Trane BCXC-SVX01B-EN Blower User Manual


 
BCXC-SVX01B-EN 31
Installation Electrical
Table 14. Motor electrical data
Voltage Voltage range rpm Rated hp lb FLA LRA
115/60/1
104–126 1750 1/3 18 5.8 22.8
1/2 21 7.2 30.4
3/4 29 12.0 58.4
1.0 29 12.8 58.4
Two-speed
115/60/1
104–126 1750/1160 3/4 40 8.9/6.1 42.0
1.0 41 11.5/8.1 58.2
208–230/60/1
187–253 1750 1/3 18 3.1 11.4
1/2 21 3.6 15.2
3/4 29 6.0 29.2
1.0 29 6.4 29.2
277/60/1
249–305 1750 1/3 15.5 2.5 12.1
1/2 21.5 3.6 19.3
3/4 25 4.3 25.3
1.0 29 5.6 32.6
208/60/3
187–229 1750 1/2 22 2.3 11.4
3/4 26 2.9 15.9
1.0 28 3.5 20.2
1.5 29 4.8 30.0
2.0 34 6.2 38.5
3.0 49 8.6 55.1
230/60/3
207–253 1750 1/2 22 2.4 12.8
3/4 26 3.0 18.6
1.0 28 3.6 23.0
1.5 29 4.8 33.4
2.0 34 6.2 43.6
3.0 49 8.6 62.0
460/60/3
414–506 1750 1/2 22 1.2 6.4
3/4 26 1.5 9.3
1.0 28 1.8 11.5
1.5 29 2.4 16.7
2.0 34 3.1 21.8
3.0 49 4.3 31.0
575/60/3
518–632 1750 3/4 20.5 1.1 7.5
1.0 22.5 1.4 9.0
1.5 31 1.9 13.3
2.0 36 2.5 17.9
3.0 49 3.3 23.7
Note: For two-speed units not being controlled by the Tracer™ family of controls, a 0.2-second delay for speed switching needs
to be incorporated into the control sequence.