Trane BCXC-SVX01B-EN Blower User Manual


 
BCXC-SVX01B-EN 11
Pre-Installation
Receiving and Handling
Blower coil units are packaged for easy handling and storage on the job site. Upon delivery, inspect
all components for possible shipping damage. See the “Receiving Checklist” section (below) for
detailed instructions. Trane recommends leaving units and accessories in their shipping packages/
skids for protection and handling ease until installation.
Shipping Package
Blower coil air handlers ship assembled on skids with protective coverings over the coil and
discharge openings.
Ship-Separate Accessories
Field-installed sensors ship separately inside the unit’s main control panel. Piping packages,
mixing boxes, ship separately packaged on the same skid as the unit.
Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to detect possible
shipping damage.
Inspect individual cartons before accepting. Check for rattles, bent carton corners, or other visible
indications of shipping damage.
If a unit appears damaged, inspect it immediately before accepting the shipment. Manually
rotate the fan wheel to ensure it turns freely. Make specific notations concerning the damage on
the freight bill. Do not refuse delivery.
Inspect the unit for concealed damage before it is stored and as soon as possible after delivery.
Report concealed damage to the freight line within the allotted time after delivery. Check with the
carrier for their allotted time to submit a claim.
Do not move damaged material from the receiving location. It is the receiver’s responsibility to
provide reasonable evidence that concealed damage did not occur after delivery.
Do not continue unpacking the shipment if it appears damaged. Retain all internal packing,
cartons, and crate. Take photos of damaged material if possible.
Notify the carrier’s terminal of the damage immediately by phone and mail. Request an
immediate joint inspection of the damage by the carrier and consignee.
Notify your Trane representative of the damage and arrange for repair. Have the carrier inspect
the damage before making any repairs to the unit.
Compare the electrical data on the unit nameplate with the ordering and shipping information
to verify the correct unit is received.
Jobsite Storage Recommendations
This unit is intended for indoor use only. To protect the unit from damage due to the elements and
prevent it from possibly becoming a contaminant source for IAQ problems, store the unit indoors.
If indoor storage is not possible, the Trane Company makes the following provisions for outdoor
storage:
1. Place the unit(s) on a dry surface or raised off the ground to assure adequate air circulation
beneath unit and to assure that no portion of the unit contacts standing water at any time.
2. Cover the entire unit with a canvas tarp only. Do not use clear, black, or plastic tarps as they
may cause excessive moisture condensation and equipment damage.
Note: Wet interior unit insulation can become an amplification site for microbial growth (mold),
which may cause odors and health-related indoor air quality problems. If there is visible
evidence of microbial growth (mold) on the interior insulation, remove and replace the
insulation prior to operating the system.