Trane BCXC-SVX01B-EN Blower User Manual


 
60 BCXC-SVX01B-EN
Start-Up
Zone Sensor
The Tracer™ ZN controller accepts the following zone sensor module inputs:
Space temperature measurement (10kW thermistor)
Local setpoint (either internal or external on the zone sensor module)
Fan mode switch
Timed override, using “on” and “cancel” buttons (Tracer ZN510 and ZN520 only)
Communication jack (Tracer ZN510 and ZN520 only)
Space Temperature Measurement
Zone sensors use a 10kW thermistor to measure the space temperature. Wall-mounted zone
sensors include a space temperature thermistor. Unit-mounted zone sensors have a return air
sensor mounted in the unit’s return airstream. If both a hardwired and communicated space
Table 29. Binary output configuration
Binary output
pin connection Configuration ZN010 ZN510 ZN520
J1-1 Fan high •••
J1-2 N/A •••
J1-3 Fan low
J1-4 (Key)
Fan low ••
J1-5 Main valve – open, or 2 pos. valve
(a)
(a) Two-pipe hydronic heat/cool changeover units use terminals J1-5 and J1-6 to control the primary valve for both heating and
cooling. Units configured and applied as 2-pipe hydronic heat/cool changeover with electric heat, use terminals J1-5 and
J1-6 to control the primary valve (for both cooling and heating), and terminals J1-9 and J1-10 for the electric heat stage.
For those 2-pipe changeover units, electric heat will not energize while the hydronic supply is hot (5 or more degrees
above the space temperature). In a 4-pipe application, pin J1-5 is for cooling and pin J1-6 for heating.
•••
J1-6 Aux. valve/elec. ht. ••
Aux. valve – close
(a)
J1-7 2-pos. damper ••
J1-9 Heat valve – open, or 2 pos. valve, or first stage elec. ht.
(a)
J1-10 Heat valve – close or sec. stage elec. ht.
(a)
J1-11 Fresh air damper – open
J1-12 Fresh air damper – close
TB4-1 Generic / baseboard heat output
TB4-2 24 VAC
Notes:
1. If no valves are ordered with the unit, the factory default for Tracer™ ZN010 and ZN510 controllers are: main valve
configured as normally closed and aux. valve configured as normally open.
2. If the fresh air damper option is not ordered on the unit, 2-pos. damper is configured as none.
3. Pin J1-2 can be configured for an exhaust fan with the use of Rover™ software. Factory default is none.
Table 30. Zone sensor wiring connections
TB1 Description
1Space temperature
2Common
3Setpoint
4Fan mode
5 Communications
6 Communications