LG Electronics C Series Portable Generator User Manual


 
Chapter 9. Basic functions
9.6 Stop mode select
z Decel to stop
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Function
group 1
F4 [Stop mode select] 0
0/2 0
Set F30 to 0 {Decel to stop}.
The inverter decelerates to 0Hz for the preset time.
Run
command
Freq.
Decel time
z DC brake to stop
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Function
group 1
F4 [Stop mode select] 1
0/2 0
Set F30 to 1 {DC brake to stop} (See page 10-1 for more).
z Free run to stop
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Function
group 1
F4 [Stop mode select] 2
0/2 0
Set F30 to 2 {Free run to stop}.
The inverter turns off the output frequency and voltage when the run command is OFF.
Run
command
Freq, Voltage
76