LG Electronics C Series Portable Generator User Manual


 
Chapter 9. Basic functions
z Power On Start select
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Drive
group
drv
[Drive mode]
(Run/Stop mode)
1, 2
0/3 1
Function
group 2
H20 [Power On Start select] 1
0/1 0
Set H20 to 1.
When AC input power is applied to the inverter with drv set to 1 or 2 {Run via control terminal} ON,
motor starts acceleration.
This parameter is inactive when the drv is set to 0 {Run via keypad}.
CAUTION
Particular attention must be directed to this function due to potential hazard as motor
starts to run suddenly upon applying AC input power.
Run
command
Frequency
Input voltage
When H20 is 0 When H20 is 1