LG Electronics C Series Portable Generator User Manual


 
Chapter 9. Basic functions
z Multi-Accel/Decel time setting via Multi-function terminals
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
ACC [Accel time] - 0/6000 5.0 Sec
Drive
group
dEC [Decel time] - 0/6000 10.0 Sec
I20
[Multi-function input
terminal P1 define]
0 0
I21
[Multi-function input
terminal P2 define]
1 1
I22
[Multi-function input
terminal P3 define]
8
2
I23
[Multi-function input
terminal P4 define]
9
3
I24
[Multi-function input
terminal P5 define]
10
0/24
4
I34 [Multi-Accel time 1] - 3.0
~ ~
I/O group
I47 [Multi-Decel time 7] -
0/6000
9.0
Sec
Set I22, I23, I24 to 8, 9, 10 if you want to set Multi - Accel/Decel time via P3-P5 terminals.
Multi-Accel/Decel time 0 is settable at ACC and dEC.
Multi-Accel/Decel time 1-7 is settable at I34-I47.
Frequency
P3
P4
P5
FX
Accel
Time 0
Accel
time 1
Accel
time 2
Accel
time 3
Decel
time 4
Decel
time 5
Decel
time 6
Decel
time 7
Multi-
Accel/Decel
time
P5 P4 P3
0 - - -
1 - -
9
2 -
9
-
3 -
9 9
4
9
- -
5
9
-
9
6
9 9
-
7
9 9 9
72