Chapter 11. Monitoring
11.5 Multi-function output terminal (MO) and Relay (30AC)
Group
LED
display
Parameter Name Setting
Factory
default
0
FDT-1
I54
[Multi-function
output terminal
select]
1
FDT-2
2
FDT-3
I55
[Multi-function
relay select]
3
FDT-4
4
FDT-5
5
Overload {OL}
6
Inverter Overload {IOL}
7
Motor stall {STALL}
8
Over voltage trip {OV}
9
Low voltage trip {LV}
10
Inverter heatsink overheat {OH}
11
Command loss
12
During run
13
During stop
14
During constant run
15
During speed searching
16
Wait time for run signal input
17
Fault output
12
I56
[Fault relay
output]
When
setting the
H26–
[Number
of auto
restart
tries]
When the
trip other
than low
voltage
trip occurs
When the
low
voltage
trip occurs
Bit 2 Bit 1 Bit 0
0
- - -
1
- -
9
2
-
9
-
3
-
9 9
4
9
- -
5
9
-
9
6
9 9
-
I/O group
7
9 9 9
2
Select the desired item to be output via MO terminal and relay (30AC).
105