LG Electronics C Series Portable Generator User Manual


 
Chapter 9. Basic functions
9.2 Multi-Step frequency setting
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency command] 5.0 0/400 0.0 Hz
Frq [Frq mode] 0 0/8 0 -
St1
[Multi-Step frequency 1]
- 10.0
St2
[Multi-Step frequency 2]
- 20.0
Drive
group
St3
[Multi-Step frequency 3]
-
0/400
30.0
Hz
I22
[Multi-function input
terminal P3 define]
5
2 -
I23
[Multi-function input
terminal P4 define]
6
3 -
I24
[Multi-function input
terminal P5 define]
7
0/24
4 -
I30 [Multi-Step frequency 4] - 30.0
I31 [Multi-Step frequency 5] - 25.0
I32 [Multi-Step frequency 6] - 20.0
I/O
group
I33 [Multi-Step frequency 7] -
0/400
15.0
Hz
Select a terminal to give Multi-step frequency command among P1-P5 terminals.
If terminals P3-P5 are selected for this setting, set I22-I24 to 5-7 to give Multi-step frequency
command.
Multi-step frequency 0 is settable using Frq – [Frequency mode] and 0.0 – [Frequency command].
Multi-step frequency 1-3 are set at St1-St3 in Drive group, while Step frequency 4-7 are set at I30-
I33 in I/O group.
Step
freq
FX or RX P5 P4 P3
0
9
- - -
1
9
- -
9
2
9
-
9
-
3
9
-
9 9
4
9 9
- -
5
9 9
-
9
6
9 9 9
-
7
9 9 9 9
Frequency
P3
P4
P5
FX
RX
Step 0
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Step 0
65