CHAPTER 3 - PARAMETER LIST
3.1 Drive Group [DRV]
Code Description
Keypad
Display
Setting Range Units
Factory
Default
Adj.
During
Run
Page
DRV-00
Output Frequency during running,
Reference Frequency during stop
0.00
0.00 to (FU1-20) 0.01 00.00 [Hz] Yes 34
DRV-01 Acceleration Time
ACC
0.0 to 999.9 [sec] 0.1 10.0 [sec] Yes 34
DRV-02 Deceleration Time
DEC
0.0 to 999.9 [sec] 0.1 20.0 [sec] Yes 34
0 (keypad)
1 (Fx/Rx-1)
2 (Fx/Rx-2)
DRV-03
Drive Mode
(Run/Stop Method)
Drv
3 (RS485)
- 1 (Fx/Rx-1) No 35
0 [Keypad-1]
1 (Keypad-2)
2 (V1)
3 (I)
4 (V1+I)
DRV-04
Frequency Mode
(Freq. Setting Method)
Frq
5 (RS485)
- 0 [Keypad-1] No 35
DRV-05 Step Frequency 1
St1
10.00 [Hz]
DRV-06 Step Frequency 2
St2
20.00 [Hz]
DRV-07 Step Frequency 3
St3
0.00 to (FU1-20) 0.01
30.00 [Hz]
Yes 36
DRV-08 Output Current
Cur
* [A] - - [A] - 36
DRV-09 Motor Speed
RPM
* [rpm] - - [rpm] - 36
DRV-10 DC link Voltage
DCL
* [V] - - [V] - 37
DRV-11 User Display Selection
vOL,
Por,
tOr
Selected in FU2-73
(User disp)
- - - 37
DRV-12 Fault Display
nOn -
-
None
nOn
- 37
F (Forward)
DRV-13 Motor Direction Set
drc
r (Reverse)
- F (Forward) Yes 37
DRV-20 FU1 Group Selection
FU1
38
DRV-21 FU2 Group Selection
FU2
38
DRV-22 I/O Group Selection
I O
38