PROGRAMMING AND OPERATION
36
Total Control Menus (System configuration must indicate Total Control configuration and is automatically
detected when the electrical connections are made between the #75003 and #75001 systems)
Set pH overfeed (Range: No pH overfeed - 120 minutes in 5 minute increments) (Used to stop the chlorine and acid feed if the pH
set point is not reached in the user programmed time.)
1. Press MENU, press ∆ or ∇ until “Maintenance menu” is displayed, then press SELECT.
2. Press
∆ or ∇ until “pH overfeed” is displayed, then press SELECT (No pH overfeed is the factory setting).
3. Press
∆ or ∇ to the desired overfeed time setting, then press SELECT.
4. Press
∆ or ∇ until “End menu mode” is displayed, then press SELECT.
Set pH min (Used to set the lower limit of pH adjustment before a warning message is displayed)
1. Press MENU, press ∆ or ∇ until “Maintenance menu” is displayed, then press SELECT.
2. Press
∆ or ∇ until “Set pH min” is displayed, then press SELECT (6.5 is the factory setting).
3. Press
∆ or ∇ to the desired pH min setting, then press SELECT.
4. Press
∆ or ∇ until “End menu mode” is displayed, then press SELECT.
Set pH max (Used to set the upper limit of pH adjustment before a warning message is displayed)
Note: For safety reasons, acid will not feed when measured above the programmed pH max.
1. Press MENU, press ∆ or ∇ until “Maintenance menu” is displayed, then press SELECT.
2. Press
∆ or ∇ until “Set pH max” is displayed, then press SELECT (8.0 is the factory setting).
3. Press
∆ or ∇ to the desired pH max setting, then press SELECT.
4. Press
∆ or ∇ until “End menu mode” is displayed, then press SELECT.
Calibrate pH (Used to match the pH display of the Digital to the results of a reliable pH test kit)
1. Press MENU, press ∆ or ∇ until “Maintenance menu” is displayed, then press SELECT.
2. Press
∆ or ∇ until “Calibrate pH” is displayed, then press SELECT (the pH sensor measurement will be displayed).
3. Press
∆ or ∇ to match a reliable pH test result, then press SELECT.
4. Press
∆ or ∇ until “End menu mode” is displayed, then press SELECT.
Enable / Disable ORP (Used to temporarily enable or disable the ORP control system, thus disabling the chlorine generation)
1. Press MENU, press ∆ or ∇ until “Maintenance menu” is displayed, then press SELECT.
2. Press
∆ or ∇ until “Enable ORP or Disable ORP” is displayed, then press SELECT.
• if “Enable ORP” then the ORP sensor is disabled, press SELECT to enable the ORP sensor.
• if “Disable ORP” then the ORP sensor is enabled, press SELECT to disable the ORP sensor.
3. Press
∆ or ∇ until “End menu mode” is displayed, then press SELECT.
Set ORP overfeed (Range: No ORP overfeed - 120 minutes in 5 minute increments) (Used to stop the chlorine and acid feed if
the ORP set point is not reached in the user programmed time.)
1. Press MENU, press ∆ or ∇ until “Maintenance menu” is displayed, then press SELECT.
2. Press
∆ or ∇ until “ORP overfeed” is displayed, then press SELECT (No ORP overfeed is the factory setting).
3. Press
∆ or ∇ to the desired overfeed time setting, then press SELECT.
4. Press
∆ or ∇ until “End menu mode” is displayed, then press SELECT.