Inverter/Charger Installation
2–2 975-0239-01-01
Pre-Installation
Before installing the XW Inverter/Charger, read all instructions and cautionary markings
located in this manual.
Location
The XW Inverter/Charger is certified for indoor (heated or unheated) installations only.
Close to battery
bank
Locate the inverter as close to the batteries as possible in order to keep the battery cable
length short. The maximum recommended battery cable length is 10 feet (3 m).
Locate any electronic equipment susceptible to radio frequency and electromagnetic
interference as far away from the inverter as possible.
Fire safety Do not locate the inverter near readily flammable materials such as cloth, paper, straw, or
plastic sheeting. Flammable materials should be kept a minimum distance of 24 inches
(60 cm) from the top surface and 12 inches (30 cm) from either side surface and the front
of the XW Inverter/Charger.
Knockout Preparation
Remove your choice of knockouts from the chassis to facilitate conduit installation for
wire runs. Ensure no debris from this procedure remains inside the inverter enclosure.
Important:
Be sure to obtain the appropriate permits, if necessary, prior to
starting this installation. Installations must meet all local codes and standards.
Installations of this equipment should only be performed by skilled personnel
such as qualified electricians and Certified Renewable Energy (RE) System
installers.
WARNING: Personal Injury
The XW Inverter/Charger weighs approximately 120 pounds (54 kg). To prevent personal injury,
always use proper lifting techniques and have someone available to assist with lifting during
installation.
WARNING: Explosion and Corrosion Hazard
Do not locate the inverter directly above the batteries or in the same compartment as vented
batteries.
Important:
Do not drill, cut, or punch holes into the XW power distribution
Panel. Use only the knockouts provided for conduit entry.