Mechanical Specifications
975-0320-01-01 A–5
Display Accuracy
Mechanical Specifications
Regulatory Approvals
The GT Inverter has complete on-board over-current, over-temperature and
anti-islanding protection, and meets U.S., Canadian and international safety
operating standards and code requirements:
UL 1741 1st Edition 2005 Revision – Standard for Inverters, Converters,
Controllers and Interconnection System Equipment for Use with Distributed
Energy Resources (Includes IEEE 1547 and 1547.1)
CSA C22.2 No. 107.1-01 General Use Power Supplies
IEEE C62.41.2 – IEEE Recommended Practice on the Characterization of
surges in Low-Voltage AC Power Circuits (Location Category B). Part of UL
1741-2005. Refer to approval certificate for details.
Instantaneous Power +/- (30 W + 1% of reading)
Voltage +/- (1% of rating + 1% of reading)
Current +/- (1% of rating + 1% of reading)
System Lifetime energy +/- 5%
Outdoor enclosure NEMA 3R, Rainproof
Inverter dimensions
(H × W × D)
28.5 × 15.9 × 5.7 inches (72.4 × 40.3 × 14.5 cm)
Shipping dimensions
(H × W × D)
34.1 × 20.4 × 10.3 inches (86.6 × 51.8 × 26.2 cm)
Inverter weight 58 lb (26.3 kg)
Shipping weight 76 lb (34.5 kg)
Input and output
terminals
AC and DC terminals accept wire sizes of 2.5 to 16 mm
2
(#14 to #6 AWG)
Disconnect switch Integrated switch, disconnects both AC and DC
(meets NEC article 690), rated @ 600 Vdc
Note: This inverter is compliant with IEEE 1547 for those requirements referenced in
UL1741 (2005), section 46.1.1.:
A utility interactive inverter and interconnection system equipment (ISE) shall comply
with the Standard for Interconnecting Distributed Resources With Electric Power
Systems, IEEE 1547, and the Standard for Cofnformance Test Procedures for Equipment
Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547.1,
excluding the requirements for Interconnection Installation Evaluation, Commissioning
Tests, and Periodic Interconnection Tests.