Xantrex Technology Automatic Generator Portable Generator User Manual


 
Fault Messages
975-0082-01-01 5–5
Fault Messages
When the Auto Gen Start detects a fault condition, it stops the generator.
The red Fault light also comes on, and the System Control Panel displays
a fault message.
The Auto Gen Start remembers the AGS Mode that it was in at the time it
detected the fault. After you have cleared the fault, the Auto Gen Start
returns to its last known AGS Mode.
W250 The selected value
failed to change.
Try again.
No You have tried to change
the Gen Type without
putting the system into
Safe mode first.
Press “continue.” Put the
system into Safe mode,
change the Gen Type, then
return the system to
Operating mode.
You have tried to set the
“Exercise Dur” for longer
than “Max Run Time,” or
“Max Run Time” for less
than “Exercise Dur.”
Press “continue.” Ensure
that “Max Run Time” is set
for longer than “Exercise
Dur.”
W500 Network
connection lost.
Check connections.
Yes The Auto Gen Start has lost
communications with the
network because of a faulty
connection or electronic
signal disruption.
Check connection between
the Auto Gen Start and the
network.
W501 AGS has fixed
memory problem
and restored default
settings.
No The Auto Gen Start
encountered an internal
memory problem upon
startup. To remain
operational, the Auto Gen
Start restored its default
settings.
Acknowledge the warning
and reset configurable
settings if necessary.
Table 5-1
Auto Gen Start warning messages
Warning
Number Message
Self-
clearing? Cause Action