Xantrex Technology Automatic Generator Portable Generator User Manual


 
Configuration
3–8 975-0082-01-01
Gen Status
Full name Generator Operating Status
Purpose “Gen Status” reports the current operating state of the generator. You
cannot adjust any “Gen Status” values.
Gen Trigger
Purpose “Gen Trigger” reports the source of the active generator start trigger. Start
triggers can include battery voltage, inverter load, battery state of charge,
thermostat triggers, or exercise period. You cannot adjust any “Gen
Trigger” values.
Value Description
On The generator is running.
Off The generator is not running.
Fault A fault condition exists. The Auto Gen Start is not controlling the
generator, or the Auto Gen Start has an internal fault. If the generator
is still running in a fault state, it may be stopped at the generator or by
one of the generator’s control panels. See “AGS Mode” and
“Troubleshooting” on page 5–1.
Value Description
NotOn Generator is not running
LowBattV Preset minimum battery voltage with associated time delay
CntctClosed Activated thermostat 1 or 2
BattSOCLow Preset minimum battery state of charge
ACIHigh Preset maximum inverter load current
Exercise Preset exercise period, exercise time, and exercise duration
ManualOn Started manually using System Control Panel
ExtOnviaAGS Started by external switch connected to Auto Gen Start
ExtOnviaGen Started by switch connected to generator
UnableToStop Auto Gen Start has lost control of the running generator