Xantrex Technology Automatic Generator Portable Generator User Manual


 
Installation
2–12 975-0082-01-01
Type 3
Type 3 is a three-wire GlowStop with shutdown bypass configuration.
The configuration shown in Figure 2-5 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown
functionality during cranking. (Generators with this functionality often
have a manual means of disabling it during cranking.)
Figure 2-5
Type 3 connection diagram
Table 2-4
Type 3 relay and timing preset configurations
Relay 1 mode
GlowStop/Shutdown bypass
Relay 3 mode
Preheat/Shutdown bypass
Gen Run signal hold time
0.5 s
Preheat time
20 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Shutdown bypass time
10 s
Start tries
3
PREHEAT
BYPASS SHUTDOWN
STOP
14
13
12
GEN RUN SIGNAL
GROUND
18
17
START
16
Relay 1
Relay 2
5A fuse
5A fuse
Generator wireAGS wiring harness wire
Complete overcurrent protection
not shown. Refer to page 2–6.