Xantrex Technology Automatic Generator Portable Generator User Manual


 
Troubleshooting
5–4 975-0082-01-01
W204 Manual Off: Max
generator cycles
reached. Reset AGS
Mode.
No The generator has reached
its maximum number of
start-and-stop cycles. To
help prevent an unattended
generator from starting, the
Auto Gen Start changed the
AGS Mode to ManualOff.
Acknowledge the warning.
Return the Auto Gen Start
to the desired AGS Mode
(Automatic or ManualOn).
Ensure generator is fueled
and is supplying required
power for battery charging
and loads.
W205 Generator started
by its switch. Use
its switch to stop.
Yes The generator was started,
but not by the Auto Gen
Start.
Check your generator. Stop
it using the switch or
control panel on the
generator.
W206 Mismatched
triggers. Enable
stop trigger or
disable start trigger.
No You have set a start trigger,
but not a corresponding
stop trigger.
Acknowledge warning and
set a stop trigger.
W207 Mismatched
triggers. Enable
start trigger or
disable stop trigger.
No You have set a stop trigger,
but not a corresponding
start trigger.
Acknowledge warning and
set a start trigger.
W208 Auto triggers not
enabled. Config
auto triggers
No You are attempting to enter
Automatic Mode without
setting Auto triggers.
Acknowledge warning and
set a start and stop trigger.
W209 Gen external stop.
Start gen via its
control panel.
Yes The generator has stopped,
but not by the Auto Gen
Start. The generator may
have run out of gas, or may
have been shut off by a
switch on the generator.
Check the generator’s fuel
level and mechanical
condition, then start the
generator manually (using
the switch or control panel
on the generator) to clear
the warning.
Table 5-1
Auto Gen Start warning messages
Warning
Number Message
Self-
clearing? Cause Action