Xantrex Technology Automatic Generator Portable Generator User Manual


 
Installing the Auto Gen Start
975-0082-01-01 2–15
Type 6
Type 6 is a three-wire GlowStop configuration that has a normally closed
Run/Stop contact. This generator type is intended for Yamaha generators.
Type 7
Type 7 will work with both two-wire and three-wire run mode
configurations that require a preheat signal before cranking, such as
Generac Backup/Renewable generators. This Gen Type setting is suitable
for generators with an automatic engine cranking control system (two-
wire) and generators that require that the Auto Gen Start control their
starter separately (three-wire).
Figure 2-7
Type 6 connection diagram
Table 2-7
Type 6 relay and timing preset configurations
Relay 1 mode
GlowStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
10 s
Preheat to crank delay
1 s
Crank time
15 s
Crank retry time
30 s
Shutdown bypass time
0 s
Start tries
3
18
17
START
16
15
13
12
GEN RUN SIGNAL
GROUND
PREHEAT14
STOP
Relay 2
Relay 1
5A fuse
5A fuse
5A fuse
Generator wiresAGS wiring harness
Complete overcurrent protection
not shown. Refer to page 2–6.