Xantrex Technology Automatic Generator Portable Generator User Manual


 
Warning Messages
975-0082-01-01 5–3
To view a fault list or warning list:
1. On the Select Device menu, highlight System and press Enter.
2. On the System Settings menu, highlight View Fault List or View
Warning List.
3. Press Enter.
Warning Messages
Table 5-1 provides details and suggests action for Auto Gen Start
warnings.
Table 5-1
Auto Gen Start warning messages
Warning
Number Message
Self-
clearing? Cause Action
W200 Generator was
stopped manually.
No Generator was stopped by
an external Manual Off
switch.
Acknowledge the warning.
To resume automatic starts
and stops, change the Auto
Gen Start mode to Auto.
W201 Generator was
started manually.
No Generator was started by
an external Manual On
switch
Acknowledge the warning.
To resume automatic starts
and stops, change the Auto
Gen Start mode to Auto.
W202 Unable to start
generator. AGS will
try again.
Yes The Auto Gen Start tried,
but could not start the
generator.
No action required. The
Auto Gen Start will try to
start the generator again
until it reaches the
maximum number of start
tries.
W203 Manual Off: Max
generator run time
reached. Reset AGS
Mode.
No The generator has run for
its maximum allowable
time. The Auto Gen Start
has stopped the generator
and changed the AGS
Mode to ManualOff.
Acknowledge the warning.
Return the Auto Gen Start
to the desired AGS Mode
(Automatic or ManualOn).
Ensure generator is fueled
and is supplying required
power for battery charging
and loads.