Xantrex Technology Automatic Generator Portable Generator User Manual


 
Configuration
3–22 975-0082-01-01
If the Auto Gen Start is set to Automatic mode, then the Auto Gen Start
will start the generator when the system battery voltage (as measured by
the inverter/charger) falls below the “StartV:2hr” setting for 2 hours.
See “StartV:15min” for more information.
StartV:24hr
Full name Starting Battery Voltage—24 hours
Purpose “StartV:24hr” is a changeable setting that enables the Auto Gen Start to
start the generator whenever the battery voltage reaches a pre-set voltage
for longer than 24 hours.
This setting requires you to set either “StopBattV”, or a Stop at Charge
Stage setting (“Stop Float” or “Stop Absorb”).
If the Auto Gen Start is set to Automatic mode, then the Auto Gen Start
will start the generator when the system battery voltage (as measured by
the inverter/charger) falls below the “StartV:24hr” setting for 24 hours.
See “StartV:15min” for more information.
StopBattV
Full name Stopping Battery Voltage
Purpose “StopBattV” is a changeable setting that allows the Auto Gen Start to stop
the generator whenever the battery voltage reaches a pre-set DC voltage.
This setting requires you to set a Starting Battery Voltage also. See
“StartV:30sec”, “StartV:15min”, “StartV:2hr”, and “StartV:24hr”.
When to use Use the “StopBattV” setting when you have enabled and set a Starting
Battery Voltage setting.
The “StopBattV” setting is most useful when you want the inverter/
charger to give the batteries a quick, basic charge. To give the batteries a
more complete, consistent charge, use the “Stop Float” setting.
Values Default
Off, 4.0V to 60.0V Off (disabled)
Values Default
Off, 14.0V to 60.0V
(increments of 0.1V)
Off (disabled)