Xantrex Technology Automatic Generator Portable Generator User Manual


 
The Auto Gen Start Menu
975-0082-01-01 3–23
Stopping
conditions
Whenever the generator starts automatically based on the Starting Battery
Voltage, it will shut off once the Stopping Battery Voltage has been
reached.
If “Stop Float” or “Stop Absorb” have been enabled, the Auto Gen Start
will stop the generator if the Float or Absorption stages of the battery
charging have begun.
Actual battery voltage can be monitored from the System screen on the
System Control Panel.
Outcomes If you set “StopBattV” too high, the generator may run for too long.
If you set “StopBattV” too low, the Auto Gen Start will stop the generator
before the inverter/charger has charged the batteries.
Enable Temp1
See page 3–15.
Enable Temp2
See page 3–16.
Enable Load
Full name Enable Inverter Load Start and Stop Triggers
Purpose “Enable Load” is a changeable setting that enables or disables the Start on
Inverter Load Current and Stop on Inverter Load Current functionality of
the Auto Gen Start. See “Start Load” and “Stop Load” on page 3–25.
“Enable Load” applies only when the Auto Gen Start is in Automatic
mode.
When to use When you need to use the Auto Gen Start “Start Load” (Start on Inverter
Load Current) feature, set “Enable Load” to On, then check or reset the
values you have set for “Start Load” and “Stop Load”.
Value Description
On, Off Enable or disable the Start on Inverter Load Current
and Stop on Inverter Load Current functionality.