Roberts Gorden POP-ECA/PGP-ECA 015 to 0100 Patio Heater User Manual


 
COMBAT
®
CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL
14
Figure 6: Guy Wire
Figure 7: Socket Direction
Figure 8: Flue and Roof Detail
Figure 9: Flue and Heater Spigot Joint Detail
Over 2 m
use Guy Wires
Roof
Wall
Use adequate
support to
prevent heater
from carrying
the weight of
the flue.
Male spigot
facing down.
Screws,
four typical.
Roof
Flue
Terminal
Conversion Collar -
last joint below
the roof line.
Male spigot
facing up.
Clamp Ring
Metal Sleeve
Masterflash
Soaker Flashing
or Rain Collar.
Screws
Roof
Seal Rain Collar
joint with high
temperature
silicon
sealer
Secure Bolts
Stainless Steel
Roof Tidy Plate
Heat Sealed
Flash Band
Roof Plate
Clamp ring
Screws,
four typical.
Rain Collar
Heater
Spigot
Fire
Cement
Heat
Resistant
Rope
Tidy
Plate
Screws
If it is necessary to cut any section of flue, the
cut is made at the bottom of the lowest section
where it connects to the heater.