10
4.7 Technical Data - Ecoflam Oil-Fired Burners (burner reference "G")
NOTE: For adjustment of head setting, see Ecoflam Instructions.
* Nozzle sizes are quoted in US gal/h. Fuel consumption is quoted in imperial gal/h.
Model 015 020 030 040 050 060 070 080 0100
Gross Heat Input
(kW)
(Btu/h) x (1000)
55.5
189.4
73.3
250.1
93.2
318.0
129.9
443.2
162.0
552.7
208.0
709.7
242.0
825.7
275.2
939.0
348.5
1189.1
Heat Output
(kW)
(Btu/h) x (1000)
47.4
161.8
61.2
208.9
78.4
267.4
110.2
375.9
134.5
458.8
177.7
606.5
205.3
700.3
230.4
786.2
293.4
1001.0
Burner Type Minor 8 Minor 12 Minor 20 Minor 30 Major 30
Oil Pump Connections (in) 3/8
Light Fuel Oil (Gas Oil) Data
Nozzle Size *US (gal/h) 1.00 1.50 1.75 2.50 3.50 4.00 5.00 5.00 7.00
Angle & Type 60S 60A
Make Danfoss Delavan
Head Setting (mm) 8 0 14 (full back) (fixed)
Air Setting (number) 4.2 8.5 5.5 3 4 3.7 4 6.2 1.8
Burner Fuel Pressure
(Bar)
(lbf/in
2
)
12.1
175
10.3
150
12.4
180
11.7
170
10.0
145
11.0
160
10.0
145
13.0
188
11.0
160
Fuel Consumption
(L/h)
*UK (gal/h)
5.17
1.14
6.82
1.50
8.68
1.91
12.09
2.66
15.08
3.32
19.36
4.26
22.53
4.96
25.62
5.63
32.44
7.14
Maximum Oil Pressure to
Pump Inlet
(Bar)
(lbf/in
2
)
.21
3
Kerosene Data
Nozzle Size *US (gal/h) 1.25 1.75 2.50 3.00 4.00 5.00 6.00 6.50 8.50
Angle & Type 60S 60B
Make Danfoss
Head Setting (mm) 8 0 14 (full back) (fixed)
Air Setting (number) 4 6.6 6 3 4 3.7 4.5 6 1.4
Burner Fuel Pressure
(Bar)
(lbf/in
2
)
8.6
125
9.7
140
8.3
120
9.7
140
8.3
120
9.0
130
8.3
120
9.3
135
8.3
120
Fuel Consumption
(L/h)
*UK (gal/h)
5.47
1.20
7.23
1.59
9.19
2.02
12.81
2.82
15.98
3.51
20.52
4.51
23.87
5.25
27.14
5.97
34.37
7.56