If the inverter is set in an Auto Restart Mode and normal
operation is using input power to start and stop the motor, the
inverter may be started once every two minutes. The inverter will
prevent operation if more frequent starts are commanded using
line power connection.
Synchro Starts - The Synchro Starts feature is desirable in
applications where the motor shaft is rotating at the time that
power is supplied to the motor from the inverter. If enabled the
control will automatically sense the motor rotational frequency
and immediately output that frequency at start up.
WARNING: A lightly loaded motor may suddenly
accelerate before locking in the proper
speed. Ensure that this operation will not
cause injury to personnel or damage to
driven equipment.
Parameter
82-Start Options
Value Description
0
Manual Restart. If parameter 21-OPERA
TING MODE = 2, 3, or 6
(2-Wire Control) then Run FWD or REV commands must be
removed and then re-applied to start after application of line power
.
Keypad STOP Key active as a Coast to Stop command. T
o reset
after Keypad Coast to Stop, press Keypad STOP Key again.
1
Auto Restart is active after application of line power and Run
Command is given at the Control T
erminal Strip. If parameter
21-OPERA
TING MODE = 2, 3, 4, 5, 6, or 7 then Keypad ST
OP Key
active as a Coast to Stop command. T
o reset after Keypad Coast
to Stop, press Keypad STOP Key again.
2
Synchro Start and Manual Restart. If parameter 21- OPERA
TING
MODE = 2, 3, 4, 5, 6, or 7 then Keypad ST
OP Key active as a
Coast to Stop command. T
o reset after Keypad Coast to Stop,
press Keypad ST
OP Key again.
3
Synchro Start and Auto Restart. If parameter 21-OPERA
TING
MODE = 2, 3, 4, 5, 6, or 7 then Keypad ST
OP Key active as a
Coast to Stop command. T
o reset after Keypad Coast to Stop,
press Keypad ST
OP Key again.