Baldor ID101F50-E Yard Vacuum User Manual


 
Operation
3-13
Parameter 75-RELA
Y OUTPUT SELECT
Value Description
0 Off
1 Ready
. Inactive at Fault, Low V
oltage, Idle, and in Program
Mode
2 Fault
3
Forward and Reverse Output, Output Frequency above 0.5 Hz
4
Reverse Output, Output Frequency above 0.5 Hz
5
Forward Output, Output Frequency above 0.5 Hz
6
Output Frequency less than 0.5 Hz
7
Output at Set Frequency
8
Output Frequency greater than Parameter 36-Preset Speed #4
setting
9
Running in T
orque Limit
10
Overtemperature W
arning. T
emperature is within 10 degrees
C of maximum rating
Level Two Parameter Adjustments
02-Software Revision - A view only parameter that displays the
software revision code of the installed software version.
03-Rated Current - A view only parameter that displays the
factory set nominal output current of the inverter. The factory
setting also serves as the 100% reference for all displayed
output currents. The inverter continuous output current is 110%
of the factory setting.
08-Second Fault - A view only parameter that displays the
second most recent fault condition before the Last Fault along
with the elapsed time from the last restart of the control and the
fault occurrence. The elapsed time is indicated in 0.1 hour
increments with 0.9 hour maximum displayed. The two left most
digits displayed is the fault code and the right most digits is the
elapsed time.
09-First Fault - A view only parameter that displays the most
recent fault condition before the Last Fault along with the
elapsed time from the last restart of the control and the fault