Baldor ID101F50-E Yard Vacuum User Manual


 
Operation 3-23
81-Factory Settings - If during start-up or operation you find the
control operating parameters have been adjusted to the point of
erratic or abnormal motor operation, the operating parameters
can be reset to the factory settings (1). User parameter settings
can also be stored (2) or recalled (3) for future use. The
selected option will not execute until leaving the Program Mode
and the display will prompt with SETP, STOC, or SETC when
completed. The available options are listed in the table below.
Parameter
81-Factory Settings
Value Description
0
No Action
1
Reset Parameters to Factory Settings
(Display Prompt = SETP)
2
Store User Parameter Settings
(Display Prompt = ST
OC)
3
Recall User Parameter Settings
(Display Prompt = SETC)
82-Start Options - Sets the operation of Auto Restart and
Synchro Starts. Also enables or disables the STOP key as an
E-Stop when operating from the control terminal strip and the
Stop function due to a disconnection of an external command
line connected at the control terminal strip. Please review the
following paragraphs and logic table for more information on
available selections.
Auto Restart - In the event of a power failure or inverter fault,
the Series 10 inverter can be adjusted to restart automatically.
The number of restart attempts after a fault condition can be set
by specifying the allowable number of trips within a ten minute
time period. After ten minutes has past since the first trip
occurrence, the trip counter within the microprocessor is reset to
zero. The number of allowable trips can be set by adjusting the
parameter 68-Number of Restarts. The time between a trip and
an auto restart is set by parameter 69-Restart Delay.