Baldor ID101F50-E Yard Vacuum User Manual


 
Section 2
Installation
Installation
2-1
This section describes the proper mounting and wiring of the
BALDOR Series 10 Inverter. If problems arise, please refer to
the troubleshooting information located in Section 4.
Location and Mounting
Select a mounting surface for the inverter that will allow the
control to be mounted in a vertical position using the four
mounting holes provided. The area selected should allow for
free air circulation around the control. Provide for at least five
inches of clearance on all sides for maximum cooling efficiency.
Caution: Avoid locating the inverter immediately
above or beside heat generating equipment,
or directly below water or steam pipes.
The ambient temperature around the control should not exceed
40°C. If the control is mounted into an existing control cabinet,
the ambient temperature limits should not be exceeded or failure
of the control may result. In cases where extreme temperatures
are unavoidable, a separate blower fan or cooling system should
be considered. Please contact the factory for derating of
controls operated in temperatures above 40°C.
The standard ventilated NEMA 1 enclosure should not be used
in areas where the control will be subjected to liquids, chemicals,
large amounts of airborne material (i.e. dust or lint), or explosive
atmospheres. Appropriate protection should be provided for the
inverter when used in these environments.
If the control will be subjected to levels of vibration above 0.6G,
then the inverter should be shock mounted. Excessive vibration
within the control could cause internal connections to loosen and
cause component failure or electrical shock hazard.